21
6 Setup
VEGAVIB 61 • Two-wire 8/16 mA
29268-EN-170315
Mode on the sensor
Level
Signal current - Sensor Signal lamp - sensor
Min.
Dry run protection
approx. 8 mA
Green
Min.
Dry run protection
approx. 16 mA
Red
Fault message
(min./max. mode)
any
< 2.3 mA
flashes red
VEGAVIB 61 level switch with signal conditioning instrument
1)
The following table provides an overview of the switching conditions
depending on the adjusted mode of the signal conditioning instru-
ment and the level.
Note:
Keep in mind that the mode switch of VEGAVIB 61 must be always set
to "max.".
Mode on the signal
conditioning in-
strument
Level
Signal current -
Sensor
Signal lamp - sen-
sor
Signal lamp - sig-
nal conditioning
instrument
Mode A
Overflow protection
approx. 8 mA
Green
Mode A
Overflow protection
approx. 16 mA
Red
Mode B
Dry run protection
approx. 16 mA
Red
1)
You can find suitable signal conditioning instruments in chapter "Technical
data".