C
onnection via
VEGABOX
02
P
roceed as follows
:
1
S
nap
VEGABOX
02
onto the carrier rail or
screw it to the mounting plate
2
L
oosen the cover screws and remove the
cover
3
P
ush the cable into
VEGABOX
02
through the
cable entry
4
L
oosen the screws with a screwdriver
5
I
nsert the wire ends into the open terminals
according to the wiring plan
6
T
ighten the screws with a screwdriver
7
C
heck the hold of the wires in the terminals by
lightly pulling on them
8
T
ighten the compression nut of the cable entry
.
T
he seal ring must completely encircle the
cable
9
C
onnect the supply cable according to steps
3
to
8
10
S
crew the housing cover on
T
he electrical connection is
fi
nished
.
4
.
3
W
iring plan
D
irect connection
4
1
2
2
3
F
ig
.
14
:
W
ire assignment
,
suspension cable
1
B
lue
(-):
to power supply or to the processing system
2
B
rown
(
+
):
to power supply or to the processing system
3
S
hielding
4
B
reather capillaries with
fi
lter element
C
onnection via
VEGABOX
02
1
2
–
+
1
2
3
4
5
6
1
2
3
4
5
6
F
ig
.
15
:
T
erminal assignment
VEGABOX
02
1
T
o power supply or the processing system
2
S
hielding
3
4
.
4
S
witch on phase
A
fter connecting
VEGAWELL S
51
to power supply
or after a voltage recurrence
,
the instrument carries
out a self
-
check
:
l
I
nternal check of the electronics
l
4
…
20
m
A
output jumps to the failure signal
T
he insturment delivers after this run
-
up period a
current of
4
…
20
m
A
to the cable
.
T
he value
corresponds to the actual level as well as to
settings already carried out
,
e
.
g
.
the factory setting
.
VEGAWELL S
51
19
C
onnecting to power supply
32946
-
01
-
101123