Spares and accessories
General instructions
65
cpg.1
Fully SF6 gas insulated single and double busbar GIS switchgears up to 36 kV in accordance
with IEC Standards
IG-137-EN version 03; 23/06/2016
9 Spares and accessories
Although the cubicles have been designed for a service life
in accordance with IEC 62271-200, certain components
can be replaced and installed for various reasons.
Certain spares and accessories must
be installed in the cubicle by specialised
personnel. Please check with
Ormazabal
.
If any of the stated auxiliary components need to be
changed, the corresponding spare parts kit must be
ordered, and the instructions given in the corresponding
documentation must be followed.
9.1 Preventive maintenance for the
cpg.1
cubicle
The driving mechanisms and other elements outside
the gas tank may require preventive maintenance; the
frequency of this maintenance depends on the existing
environmental conditions (harsh environments, dust,
extreme temperatures, etc.) and must be established in
line with the experience and responsibility of the installer.
Maintenance should be carried out every 5 years or 2000
operating cycles, unless, based on the conditions of use,
the user, together with
Ormazabal
, considers otherwise.
Summary of Contents for Ormazabal cpg.1 Series
Page 67: ......