2. Functional characteristics
2.1. Operating voltages
The line voltage corresponds to the rated phase-to-phase
operating voltage.
In the event that
ekor
.rtk takes the capacitive signal from
the connecting set
ormalink
, the operating voltages are
the same:
System cgmcosmos
Line voltage
3.5 - 24 kV
Table 2.1.
Cubicle operating voltages
cgmcosmos
System cgm
.3
Line voltage
3.5 - 36 kV
Table 2.2.
Ubicle operating voltages
cgm
.3
For special applications contact
Ormazabal
.
2.2. Actuation times
The
ekor
.rtk voltage detection unit takes data from the
voltages of each phase every 1.25 ms. This calculate the
r.m.s. value of each voltage and compares it with certain
pre-defined values to determine whether the voltage is
above or below the set threshold.
Where the voltage is above the voltage presence indication
threshold, a time delay of 100 ms begins. After this time,
if the voltage has remained at a value above the threshold,
the electromechanical indication relay for the corresponding
phase is opened.
When the line voltage is below the voltage absence
threshold, the relay sets at a time delay of 100 ms and closes
the indication contact of the corresponding phase.
Figure 2.1.
Diagram of times of output contact actuation
IG-094-EN version 09; 01/08/2019
5
General instructions
ekor
.rtk: Setting and assembly
of the voltage detection unit
Functional characteristics