IG-322-EN version 03; 22/07/2022
36
Operation
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
5. Operation
5.1. Switching accessories
For operation of the circuit-breaker panel the following
accessories are needed:
1.
Switching lever for earthing switch (red shaft)
(only in conjunction with 2-lever drive).
2.
Switching lever for disconnector (bare shaft)
(optional for disconnector and earthing switch (only in
conjunction with 1-lever drive)).
3.
Key for front cover fastener (controls the anti-reverse
interlock).
4.
Hand crank for circuit-breaker drive’s spring accumulator
The switching levers used to switch the circuit-breaker
panel are fitted with a non-positive lock, which prevents
damage to the drive.
When trying to continue a switching operation in a switch
position (ON/OFF) by application of force, the toggle of the
switching lever will bend.
Never leave the switching lever inserted in the
actuating shaft, because operation of the other
actuating shaft will damage the switching interlock of
the panel.