Technical description
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
4.5. Density monitor (optional)
The switchgear can be optionally fitted with a hermetically
sealed and temperature compensated density monitor
(Figure 4.4). The density monitor has one switching point.
The density monitor scale is divided into the two areas RED
and GREEN.
If the gas filling pressure drops to the defined value, the
density monitor can automatically switch off the switchgear.
A
RED => switchgear NOT ready for switching!
(Contact customer service)
B
GREEN => switchgear ready for switching!
SP
Switching point => Automatic switch off (optional)
Figure 4.4.
4.5.1. Checking the switching readiness
Danger to life due to arc fault!
The gas filling pressure must be checked prior to each
switching operation!
Read off the switching readiness of the switchgear on the
density monitor (Figure 4.4).