IG-322-EN version 03; 22/07/2022
58
Technical data
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
8. Technical data
8.1. General data
Insulating gas
SF
6
Rated density of insulating gas
7.9 kg/m
3
Rated filling pressure of insulating gas at 20 °C and 101.3 kPa
130 kPa (30 kPa overpressure)
SF
6
-filling capacity at 20 °C and 101.3 kPa
1.20 kg
Ambient temperature T
with secondary equipment
- 5 to + 40 °C
1)
average maximum value over 24 h
+ 35 °C
with reduced rated currents
above + 40 °C
Relative humidity
measured over 24 h
maximum 95 %
measured over 1 month
maximum 90 %
Enclosure of HV compartment
sealed pressure system acc. to IEC, IP 67
Internal arc classification according to IEC 62271-200
IAC AFL(R) 20 kA 1 s for HV compartment and connection compartment
Coloration of equipment
RAL 7035 (light grey)
Loss of service continuity category
LSC 2A
Partition class
PM
Weight
approx. 300 kg with relay box
+ 60 kg pressure release channel
+ 90 kg voltage transformer set
1)
Usage at lower temperatures on request
Table 8.1.
8.2. Circuit-breaker panel gae
.630
-1LSV(G) ratings
12 kV
24 kV
1)
Rated frequency
f
r
50 (60) Hz
50 (60) Hz
Rated voltage
U
r
12 kV
24 kV
Rated short-duration power-frequency withstand voltage 1 min.
U
d
28 kV
50 kV
Transient voltage rate of rise
0.34 kV/µs
0.47 kV/µs
Rated insulation level
U
p
75 kV
125 kV
Rated peak withstand current
I
p
52 kA
52 kA
Rated short-time withstand current 1 s, and 3 s
I
k
20 kA
20 kA
Rated busbar current
I
r
630 A
630 A
Rated outgoing current
I
r
630 A
630 A
Rated operating sequence
O - 0.3s - CO - 15 s - CO
2)
O - 0.3s - CO - 15 s - CO
2)
Direct current component
41 %
41 %
Rated cable-charging breaking current
I
cc
50 A
50 A
Rated line-charging breaking current
I
lc
20 A
20 A
Mechanical operating cycles (ON/OFF) Earthing switch
n
1000
1000
Mechanical operating cycles (ON/OFF) Circuit-breaker
n
10 000
10 000
Mechanical operating cycles (ON/OFF) disconnector
n
2000
2000
Class
E2 / M2 / C2
E2 / M2 / C2
1)
increased rated voltage (25 kV) optional
2)
with motorised driving unit, without motorisation: O - 0.3 s CO - 3 min - CO
Table 8.2.