F. Changing Adjustable Parameters (continued)
“Press”
button to access the following parameters:
Factory
Setting
Range / Choices
Parameter and Description
Disable
Enable,
Disable
Master Enable/Disable
Master should always be Disabled.
“Press”
button to access the following parameters if this boiler is to be used as a slave in a
multiple boiler system:
Factory
Setting
Range / Choices
Parameter and Description
None
1-8
Boiler Address
Each boiler must be given a unique address. When “Normal” slave selection order is used, the
boiler address is used by the Master Sequencer as the boiler start order. The boiler address is
also the Modbus Address when a Energy Management System is connected.
Normal
Use Boiler First,
Normal,
Use Boiler Last
Slave Selection Order
“Use Boiler First”; places the Slave in the lead permanently.
“Normal”; firing order follows boiler number (1,2,3,..) order.
“Use Boiler Last”; places the slave last in the firing order.
Factory
Setting
Range /
Choices
Parameter and Description
Local
Local,
4-20mA
Central Heat Modulation Source
This parameter should always be set to “Local”.
Local
Local,
4-20mA
Central Heat Setpoint Source
This parameter should always be set to “Local”.
Local
Local,
Modbus
Central Heat Demand Source
This parameter enables a Modbus input to be take the place of the Heating Thermostat Input:
Local
Local Heating Thermostat input is used for Central Heat demand.
Modbus Modbus input is used for Central Heat demand.
“Press”
button to access the following parameters:
Summary of Contents for K2WTC-135
Page 81: ...81 107774 02 4 18 X Domestic Hot Water Piping continued Figure 10 1 Domestic Hot Water Piping...
Page 89: ...89 107774 02 4 18 XI Wiring continued...
Page 90: ...90 107774 02 4 18 Figure 11 8 Internal Wiring Connections Diagram XI Wiring continued...
Page 101: ...101 107774 02 4 18 Lighting and Operating Instructions XII Start Up and Checkout continued...
Page 142: ...142 107774 02 4 18 XVI Repair Parts continued...
Page 145: ...145 107774 02 4 18 XVI Repair Parts continued...
Page 148: ...148 107774 02 4 18 XVI Repair Parts continued...
Page 150: ...150 107774 02 4 18 XVI Repair Parts continued...
Page 152: ...152 107774 02 4 18 XVI Repair Parts continued 120 121 122 123 124 125 126 127...
Page 159: ...159 107774 02 4 18 SERVICE RECORD DATE SERVICE PERFORMED...