Setting Day-Time and Night-Time Detector Sensitivity
The day and night time detector sensitivities are set through the Device options screen.
Go to the engineer menu, and select the point Icon
Select the Option tab. The panel displays the Options
table. Press the Options field of the device to be edited.
Note that only the following detectors can have their
sensitivity altered:-
VDOT-PY: Addressable Photoelectric Smoke Detector
VDOT-PYH: Addressable Multisensory Detector
VDOT-DPH: Addressable Dual Optical/Heat Detector
For the VDOT-PY (Addressable Photoelectric Smoke
Detector), the sensitivity can be set to Low, Normal or
High.
There can be different settings for day-time & night-
time.
For the VDOT-PYH (Addressable Multisensory Detector),
there are settings for the smoke sensor, and for the heat
sensor.
The smoke sensor can be set to Off, Low, Normal or High
(Note: setting to off will make the detector work as a
heat detector only)
.
The heat sensor can be set to Off or ON.
(Note: setting to
off will make the detector work as a smoke detector
only)
.
(Note: Setting both sensors to Off will turn off the
detector, so it will no longer report an alarm)
For the VDOT-DPH (Addressable Dual Optical/Heat
Detector), there are settings for the smoke sensor, and
for the heat sensor.
The smoke sensor can be set to Off or On
(Note: setting
to off will make the detector work as a heat detector
only)
.
The heat sensor can be set to Off or ON.
(Note: setting to
off will make the detector work as a smoke detector
only)
.
(Note: Setting both sensors to Off will turn off the
detector, so it will no longer report an alarm)