Velocity Operation Manual
www.velocitydetection.com
83
Appendix C: Cause and Effects Settings Summary
The table below shows the list of options available for each type of input (cause) and Output (Effect):
Select CAUSE
Input Type
Selection 1
Selection 2
Causes
Point
Loop Number
(Port 1-26)
Point Address
(1 - 254)
Device Port
(1-15)
•
Alarm
•
Detector Alarm
•
MCP Alarm
•
Trouble
•
Maintenance
•
Supervisory ON
•
Supervisory OFF
Local I/O
Local Module
(1-26)
Module Port
(1-6)
•
Trouble
•
Alarm
•
Supervisory ON
•
Supervisory OFF
Zone
Zone Start
(1 -254)
Zone End
(1-254)
•
Alarm
•
Detector Alarm
•
MCP Alarm
•
Trouble
•
Maintenance
•
Supervisory ON
•
Supervisory OFF
•
Mlt. devices in alarm
Panel
-
-
•
Alarm
•
Detector Alarm
•
MCP Alarm
•
Trouble
•
Maintenance
•
Supervisory ON
•
Supervisory OFF
•
Mlt. devices in alarm
•
Mlt. Zones in alarm
•
Panel KeySwitch ON
•
Panel KeySwitch OFF
Select EFFECT
Output Type
Selection 1
Selection 2
Day Delay
Night Delay
Effect
Point
Loop number
(1-26)
Point Address
(1 - 254)
Device Port
(1-15)
(0-600)
(0-600)
•
Evacuation
•
Warning
•
Beacon
•
Switch off
•
Enable
•
Disable
Local I/O
Local module
(1-26)
Module Port
(1-6)
(0-600)
(0-600)
•
Evacuation
•
Warning
•
Switch off
•
Enable
•
Disable
A.Group
A. Group start
(1-254)
A. Group end
(1-254)
(0-600)
(0-600)
•
Evacuation on sounders
•
Warning on sounders
•
Activate Beacon
•
Switch OFF SND/Beacon
•
Switch ON Relays
•
Switch OFF Relays
•
Evacuation on Outputs
•
Warning on Outputs
•
Switch off Output
•
Disable sounders
•
Enable sounders
•
Disable relays