48
110332-02 - 6/22
PHTM II
Installation, Operating & Service Instructions
Figure 14-2: Gas Valve Fuel Setting
LP Conversion
WARNING
Asphyxiation Hazard.
•
Do not attempt to operate this boiler on LP
gas without making proper adjustments to
gas valve and control. Do not convert this
boiler to LP gas without using a combustion
analyzer to verify CO does not exceed 200
ppm air free for altitudes 0 to 2,000 ft. (0 to
610 m) and 300 ppm air free for altitudes
above 2,000 ft. (610 m). (In event of high
CO, consult section 18 Troubleshooting).
•
Failure to properly convert this boiler
for use on LP gas could cause unreliable
operation at elevated carbon monoxide
(CO) levels, resulting in severe personal
injury, death or substantial property damage.
•
Do not attempt to operate 150/180 above
2,000 ft. (610 m) on LP without proper
conversion kit.
LP conversion requires (2) steps: gas valve setting
adjustment and control parameter change.
1. Use 2.5 mm hex wrench to adjust gas valve
setting from "1" to "2" (Figure 14-2).
!
3. Use keypad to enter adjust mode and change
parameter
A06
from "
0
" to "
1
".
•
Press and hold "
menu
" for 3 seconds.
•
Press "
" or "
" buttons until
PAS
is visible
and press "
enter
".
•
Press "
enter
" button while
PA1
is visible.
•
Press "
+
" or "
-
" buttons until password "
86
" is
reached and press "
enter
". Press and hold for
five seconds to adjust by increments of 10.
•
Press "
menu
" button until
PAS
is visible.
•
Press "
" button until
A
is visible and press
"
enter
".
•
Press "
" or "
" buttons until
A06
is visible
and press "
enter
".
•
Press "
+
" or "
-
" buttons to change "
0
" to "
1
".
•
Press "
menu
" 3 times to return to display
mode.
14
Start-Up and Checkout
(continued)
4. Apply yellow LP gas conversion label,
supplied with boiler literature packet, to jacket
beside rating label.
2. For 150 and 180 boiler installations with LP above
2,000 ft. (610 m), replace electrode shipped with
boiler with electrode from conversion kit 111745-
01.
High Altitude Conversion
1. Change parameter
A07
(altitude selection)
according to the following table. Control is
shipped from factory with
A07
default value of 0.
Table 14-3:
A07
Value
Altitude Selection
A07
0
0-2,000 ft. (0 to 610 m)
1
2,001-6,000 ft. (611 m to 1,828 m)
2
6,001-8,000 ft. (1,829 to 2,438 m)
3
8,001-10,100 ft. (2,439 m to 3,079 m)
WARNING
Asphyxiation Hazard.
Do not attempt to operate boiler at altitude
without making proper adjustments to control.
!
NOTICE
: No additional de-rate required for altitude
installations.