60
PHTM II
Installation, Operating & Service Instructions
110331-01 - 5/20
16
Operation
(continued)
Table 16-15: Menu
LL
LL
(visible only after password entered)
Default
Range/
Choices
Parameter and Description
Off
On/Off
L01
Lead Lag Master Enable [HEATING BOILER ONLY]
Used to "turn on" Multiple Boiler Controller
On Sequencer Master is Enabled.
Off Sequencer Master is Disabled.
0
1 through 8
L02
Lead Lag Slave Address
Each boiler must be given a unique address, address determines boiler start order.
Off
On/Off
L03
Lead Lag Outdoor Reset [HEATING BOILER ONLY]
If an outdoor sensor is installed and Lead Lag Outdoor Reset is Enabled, boiler will
automatically adjust heating zone set point temperature based on outdoor reset curve.
On Enable, calculate temperature setpoint based on outdoor temperature using a reset
curve defined by Low Outdoor Temp, High Outdoor Temp, Min Boiler Temp and CH
Setpoint and Boost Time parameters
Off Disable, do not Calculate setpoint based on outdoor temperature.
Table 16-16: Menu
2P
2P
(visible only after password entered)
Default
Range/
Choices
Parameter and Description
Off
On/Off
201
to
216
Zone 1-16 On/Off Status
(Individual Zones Only Visible when communicating zone panel zone is detected.)
0
0 - 999,999
217
to
232
Zone 1-16 cycle count
(Individual Zones Only Visible when communicating zone panel zone is detected.)
Central Heat
Setpoint
Heating Element Type
Central Heat
Setpoint
Heating Element Type
180°F to 190°F
(82.2°C to 87.8°C)
Fan Coil
100°F to 140°F
(37.8°C to 60°C)
In Slab Radiant High
Mass Radiant
160°F to 190°F
(71.1°C to 87.8°C)
Convection
Baseboard
Fin Tube
Convective
130°F to 160°F
(54.4°C to 71.1°C)
Staple-up Radiant
Low Mass Radiant
130°F to 160°F
(54.4°C to 71.1°C)
Radiant
Baseboard
140°F to 160°F
(60°C to 71.1°C)
Radiators
Table 16-17: Radiation Setpoints