34
106309-03 - 4/19
D. Stainless Steel Venting
WARNING
Asphyxiation Hazard. Follow these instructions
and the installation instructions included by
the original stainless steel venting component
manufacturers, Heat Fab, M&G/DuraVent or
Z-Flex, whichever applicable. Failure to do so
could cause products of combustion to enter the
building, resulting in severe property damage,
personal injury or death. Where a conflict arises
between Heat Fab, M&G/DuraVent or Z-Flex
instructions and these instructions, the more
restrictive instructions shall govern.
Do not mix vent components from listed
manufacturers.
Examine all components for possible
shipping damage prior to installation.
All condensate that forms in the vent must be
able to drain back to the boiler.
1. Components
a. For use on models PHNTM399C and
PHNTM500C, Velocity Boiler Works offers size
4 in. vent pipe and fittings shown in Table 19. It
is the responsibility of the installing contractor
to procure stainless steel vent system pipe and
related components.
b. Alternate listed stainless steel vent system
manufacturers and components are shown in
Tables 20 and 21.
c. Where the use of “silicone” is called for in the
following instructions, use GE RTV 106 or
equivalent for the vent collar. Seal galvanized
combustion air piping sections with any general-
purpose silicone sealant such as GE RTV102.
Seal PVC combustion air piping sections with
PVC cement.
d. Do not drill holes in vent pipe.
IV. Venting
D. Stainless Steel Venting (continued)
2. Field Installation of Stainless Steel Vent
Adapter
(see Figure 22)
a. No adapter is required for stainless steel vent
pipe unless vent diameter is reduced per Table 8.
See Table 19, 20, or 21 for adapters for reduced
vent diameter.
Boiler Model
Nominal Pipe
Diameter
Boiler Adapter
Sidewall * or Roof Termination:
Straight Termination w/Screen
Wall Thimble
PHNTM399C (reduced dia.)
PHNTM500C (reduced dia.)
3 in. (80 mm)
FS0403TR
FSBS3
FSWT3
PHNTM399C (standard dia.)
PHNTM500C (standard dia.)
PHNTM600C (reduced dia. vent)
PHNTM700C (reduced dia. vent)
PHNTM800C (reduced dia. vent)
4 in. (100 mm)
PHNTM399C &
PHNTM500C: No Adapter
Required;
PHNTM600C,
PHNTM700C,
PHNTM800C: FS0604TR
FSBS4
FSWT4
PHNTM600C (standard dia. vent)
PHNTM700C (standard dia. vent)
PHNTM800C (standard dia. vent)
6 IN. (150 mm)
No Adapter Required
FSBS6 (23
o
angle)
FSWT6
Note:
When using room air for combustion, use tee for sidewall vent termination. Termination tee part numbers: FSTT3 (3 in.), FSTT4 (4in),
FSTT6 (6 in.)
See M&G DuraVent FasNSeal literature for other required component part numbers such as straight pipe, elbows, firestops, and vent supports.
Table 20: M&G DuraVent FasNSeal Stainless Steel Vent System Components, Single Wall
NOTICE
Do not exceed maximum vent/combustion
air system length. Refer to “2. Vent/
Combustion Air Piping” under “A. General
Guidelines” in this section for maximum
vent/combustion air system length.
Use only vent and combustion air terminals
and terminal locations shown in “3. Vent/
Combustion Air Terminals” under “A.
General Guidelines” of this section.
Table 19: Velocity Boiler Works (Heat Fab)
Vent System Components
(Stainless Steel, 4 in. only)
Component
Part Number, 4 in.
(100 mm)
Boiler Adapter
no adapter required
Sidewall
*
or Roof Termination:
Straight
Termination w/Screen
102680-02
Straight Pipe, 1 ft. (0.3 m)
100176-01
Straight Pipe, 3 ft. (0.9 m)
100177-01
Straight Pipe, 5 ft. (1.5 m)
100178-01
Straight Pipe, Adjustable
1.06-1.64 ft. (0.3 m to 0.5 m)
100179-01
90° Elbow
100180-01
45° Elbow
100181-01
Horizontal Drain Tee
100182-01
Vertical Drain Tee
100183-01
Single Wall Thimble
100184-01
* Note
: when using room air for combustion, use tee for
sidewall vent termination.
Tee part number: 8116313 (4 in.).
Summary of Contents for Phantom-X Series
Page 49: ...49 106309 03 4 19 VI Water Piping and Trim continued Figure 28 Near Boiler Piping Heating Only...
Page 63: ...63 106309 03 4 19 VIII Electrical continued Figure 40 Ladder Diagram...
Page 64: ...64 106309 03 4 19 VIII Electrical continued Figure 41 Wiring Connections Diagram 2...
Page 73: ...73 106309 03 4 19 IX System Start up continued Figure 47 Operating Instructions...
Page 124: ...124 106309 03 4 19 XIII Service Parts continued...
Page 130: ...130 106309 03 4 19 XIII Service Parts continued...
Page 133: ...133 106309 03 4 19 XIII Service Parts continued 10A 10B 10C 10D 10G...
Page 139: ...139 106309 03 4 19...