VII. Venting
I. Condensate Trap and Drain Line (continued)
WARNING
Asphyxiation Hazard. Failure to install the condensate drain in accordance with the above instructions
could cause flue gas to enter the building, resulting in personal injury or death.
NOTICE
Boiler condensate is corrosive. Route condensate drain line in a manner such that any condensate
leakage will not cause property damage.
Some jurisdictions may require that condensate be neutralized prior to disposal.
Use materials approved by the authority having jurisdiction.
Figure 7.46
:
Condensate Trap Installation
8. If the point of condensate disposal is above the trap, it will be necessary to use a condensate pump to move the condensate
to the drain. In such cases, select a condensate pump that is approved for use with condensing boilers. If overflow from this
pump would result in property damage, select a pump with an overflow switch and use this switch to shut down the boiler.
Alternatively, if heat is a necessity, use the overflow switch to trigger an alarm.
9. Do not attempt to move the trap from the location shown in
Figure 7.46.
Do not attempt to substitute another trap for the one
provided with the boiler.
BOILER JACKET
CONDENSATE DRAIN
INLET NUT
INLET GASKET
VENT
CORRUGATED
DRAIN TUBE
#8-18 THREAD FORMING
SCREW (1/4" LONG)
Summary of Contents for Raptor RPTR085
Page 1: ...1...
Page 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued...
Page 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued...
Page 88: ...88 X Wiring continued...
Page 97: ...97 Operating Instructions XI Start Up and Checkout continued...
Page 142: ...142 XV Repair Parts continued 3A 3B 3C 3D 3F 3E 3G 3H 3O 3P 3Q 3R 3J 3K 3I 3M 3N 3L All Models...
Page 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models...
Page 172: ...172...