Boiler 

Size

Fuel

Acceptable Combustion Readings

Approximate Derate per 1000 Ft.

Measured 

% CO

2

Measured

% O

2

Max CO

(PM Air-Free)

4501 - 7800 ft. *

(1350 - 2377 m)

7801 - 10200 ft. **

(2377 - 3109 m)

80

NG

8.7-9.1

4.9-5.6

200

0.0%

3.1%

LP

100

NG

8.5-9.3

4.5-6.0

200

0.0%

3.1%

LP

9.9-10.2

5.4-5.8

200

0.9%

3.1%

120

NG

8.8-9.3

4.5-5.4

200

0.0%

3.1%

LP

9.9-10.2

5.4-5.9

200

0.5%

3.1%

150

NG

8.6-9.3

4.5-5.8

200

0.4%

3.1%

LP

9.8-10.3

5.2-6.0

200

1.2%

3.1%

180

NG

8.5-9.1

4.9-6.0

200

1.9%

3.1%

LP

9.9-10.2

5.4-5.8

200

2.4%

*

 Derate is referenced from sea level.

**

 Derate is referenced from 7800 ft.

     Example:
     1)  150 Boiler Size using natural gas installed at 6000 ft.

           Total derate = (0.4% x 6.0) = 2.4%
     2)  150 Boiler Size using natural gas installed at 8800 ft.

           Total derate = (0.4% x 7.8) + (3.1% x 1.0) = 6.22%

Fuel

Inlet Pressure (in w.c.)

4501 - 10200 Ft.

Nat. Gas

4.0-14.0

LP

11.0-14.0

Table 3:  Boiler Altitude Adjustments 4501 - 10200 Ft. (1350 - 3109 m) 

Table 4:  Acceptable Gas Inlet Pressure Range

Boiler Size

080

100

120

150

180

PIM High Altitude Repair Kit Part Number

107394-01

107394-02

107394-03

107394-04

107394-05

Altitude

4501 - 10200 Ft.

Maximum Heat Rate (RPM)

6200

7500

7050

7300

7200

Minimum Heat Rate (RPM)

1800

2000

1800

2000

1900

Absolute Maximum Heat Rate (RPM)

7720

7680

7132

7300

7385

Minimum Light-off Rate (RPM)

3500

3500

3500

3500

3500

Maximum Light-off Rate (RPM)

4000

4000

4000

4000

4000

Table 5:  High Altitude Specific Parameters