GLT-299-7-13  Rev.1 

 

 

 

Jan 24, 2022 

 

Wiring 

All wiring must conform to applicable local codes, ordinances, and 

regulations. 

Install module wiring in accordance with the appropriate wiring 

diagrams.   

 
 
 
 
 

 

Note: All wiring is power-limited and supervised. 

 

Class B (Short circuit detection is not available) 

Detectors  and EOL (10k ohm) are connected between A+ and A-  in 

VDOT-ZMU-SCI. 

A+
A-

Lin+
Lin-
Lout+
Lout-

EOL 

10kΩ

1

6

3

1

6

3

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Figure 4 

Class A (Short circuit detection is not available) 

Detectors are connected between A+

B+

and A- (B-

in VDOT-ZMU-SCI. 

B-

B+

A+
A-

Lin+
Lin-
Lout+
Lout-

1

6

3

1

6

3

Loop

-          +

TO NEXT

DEVICE

-          +

Loop

FROM PANEL OR

PREVIOUS DEVICE

Figure 5 

 

 

 

Class B (Short circuit detection is available) 

Detectors  and EOL (10k ohm) are connected between A+ and A-  in 

VDOT-ZMU-SCI. 

Refer to Figure 4. 

 

Class A (Short circuit detection is available) 

Detectors are connected between A+

B+

and A- (B-

in VDOT-ZMU-SCI. 

Refer to Figure 5. 

 

Maintenance 

Routine inspection: Ensure the module is secure and undamaged. 

 

Operation Test 

The purpose of the Operational Test is to confirm the product’s correct 

operation. 

1)  When carrying out site testing of the product, the control panel 

shall be set to “one-man-walk test mode” prior to the test. 

2)  Take any necessary precautions to limit the sounding of the alarm 

sounders/bells and any fire service summoning device. 

3)

 

Operate a detector connected to IDC of the module and  confirm 

that  the module is in alarm condition  and the input  LED (red) 

illuminates. Confirm that an alarm signal is transmitted to the 

control panel. 

Note: If the test cannot be carried out by operating the detector, test the 

area between terminal A+  and  A-

or  B+  and  B-

with appr. 2.4kΩ 

resistor to check the module. 

4) After the detector has given the alarm condition, reset the detector 

from the control panel. It may be necessary to allow a short time to 

elapse before the detector is reset. 

Note: For detector testing and cleaning information, refer to the 

instruction manual of detector. 

5) In any subtype setting, open between terminal A+ and A-

or B+ and 

B-

, and confirm that the control panel detects the open circuit. If 

subtype is set as 5-8, short between A+ and A-

or B+ and B-

, and 

confirm that the control panel detects the short circuit.   

6) Short between terminal Lin+ (Lout+) and Lin- (Lout-), and the SCI 

LED  (yellow) is illuminated. The short circuit isolator isolates the 

devices connected after the short-circuited area, which makes these 

devices have no response. Upon removal of the short condition, the 

area is automatically connected to go back to the normal operating 

status, and the SCI LED (yellow) turns off. 

 

Do not connect cables in reverse polarity. Failure to connect the polarity 
correctly could result in damage to the module and/or other equipment.

CAUTION

!

Use cable AWG12-22 for wiring. Do not connect different gauge cables 

at one terminal in order to prevent loosening. Use a fork terminal for 

crimping two cables. 

CAUTION

!