background image

 

 

                         
www.velocitydetection.com                        Doc:   GLT-313-7-1                      Issue: 001                              Date: 28/10/2020

 

 

 

 

4) Special Conditions for Safe Use 

 

Special Condition for safe Use as stated on the Type Examination 
Certificate DEMKO 14 ATEX 4786493904X / CoC IECEx ULD 
14.0004X:  
 

End user shall adhere to the manufacturer’s installation and 

instruction when performing housekeeping to avoid the potential 
for hazardous electrostatic charger during cleaning, by using a damp 
cloth.  
 
The D2xC1 is not to be mounted with the horn facing upwards  
The equipment shall only be used in end use with appropriately 
certified cable entry devices and blanking plugs 

4.1 Installation  

 
The product must only be installed by suitably qualified personnel in 
accordance with the latest issues of the relevant standards.  
 
The installation of the units must also be in accordance with any 
local codes that may apply and should only be carried out by a 
competent electrical engineer who has the necessary training.  
 
The equipment is not to be mounted with the horn facing upwards.  
 
The equipment has not been assessed as a safety-related device (as 
referred to by Directive 94/9/EC Annex II, clause 1.5).  
 
The cable entry temperature may 70ºC / the cable 
branching point may exceed 80ºC. Therefore suitable heat resisting 
cables and cable glands must be used, with a rated service 
temperature of at least 90ºC  
 
To maintain the ingress protection rating and mode of protection, 
the M20 x 1.5 cable entries must be fitted with suitably rated, 
certified cable glands and/or suitably rated, certified blanking 
devices during installation. If a high IP (Ingress Protection) rating is 
required, then a suitable sealing washer must be fitted under the 
cable gland. For use in explosive gas atmospheres a minimum 
ingress protection rating of IP54 must be maintained. For use in 
explosive dust atmospheres a minimum ingress protection rating of 
IP64 must be maintained.  
 
Only the front cover is to be used for access to the enclosure for 
installation, service and maintenance. Once the product is opened, 
the Type Rating cannot be maintained anymore unless a full 
verification of the gasket material is done and there is no damage.  
 
Connections are to be made into the terminal blocks using solid or 
stranded wire, sizes 0.5-2.5mm2 / AWG 20-14. Wire insulation 
needs to be stripped 6-7mm. Wires may be fitted securely with 
crimped ferrules. Terminal screws need to be tightened down with a 
tightening torque of 0.56 Nm / 5 Lb-in.  
 
Internal earthing connections should be made to the internal earth 
terminal on the PCBA. The earth conductor should be at least equal 
in size and rating to the incoming power conductors. The internal 
earth bonding wire connects the PCBA earth terminal to the internal 
earth terminal in the enclosure back box. 

External earthing connections should be made to the M5 earth stud, 
using a ring crimp terminal to secure the earth conductor to the 

earth stud. The external earth conductor should be at least 4mm

AWG 11 in size. 

Check that the earth bonding wire between the two castings is 

secure and the ‘O’ ring seal is in place and in good condition. 

 

 

4.2 Maintenance, Overhaul and Repair  

 
Maintenance, repair and overhaul of the equipment should only be 
carried out by suitably qualified personnel in accordance with the 
current relevant standards: 
  
EN60079-19 / IEC60079-19 Explosive atmospheres - Equipment 
repair, overhaul and reclamation  
 
EN 60079-17/ IEC60079-17 Explosive atmospheres - Electrical 
installations inspection and maintenance 
  
Units must not be opened while an explosive atmosphere is present.  
 
If opening the unit during maintenance operations a clean 
environment must be maintained and any dust layer removed prior 
to opening the unit.  
 
Electrostatic charging hazard - Clean only with a damp cloth 

 

D2xC1 Alarm Horn and Strobe should only be installed by trained 
competent personnel.  
 

5.1 Mounting  

 
The D2xC1 Alarm Horn and Strobe may be secured to any flat 
surface using the two 9.7 x 6.7mm, 147mm pitch fixing holes. The 
enclosure provides IP66 protection and is suitable for installation in 
exterior locations providing it is positioned so that water cannot 
collect in the horn, and the cable entry is sealed. 

5.2 Installation procedure 

 

a)  

Secure the D2xC1 Alarm Horn and Strobe to a flat surface 
via the two 9.7 x 6.7mm, 147mm pitch fixing holes in the 
mounting feet.  

b)  

Remove the front of the unit by unscrewing the four 
captive cover screws and pulling the front away from the 
enclosure.  

c)  

Fit an M20x1.5 suitably rated, certified cable gland or 
conduit entry into the hole in the enclosure and connect 

 

 VL-D2xC1X05 Explosion Proof Horn Alarm & Strobe

 

Summary of Contents for VL-D2 C1X05 Series

Page 1: ...BE FREE OF IGNITIBLE CONCENTRATIONS DO NOT PAINT NE PAS PEINTURER 3 Ratings and Markings 3 1 ATEX IECEx certification The D2xC1 Alarm Horn and Strobe complies with the following standards EN60079 0 2...

Page 2: ...2 FG T5 Ta 40 C to 50 C Class III Div 1 2 Ta 40 C to 50 C Installation must be carried out in compliance with the National Electric Code Canadian Electric Code 3 5 Ambient Temperature Range 40 C to 70...

Page 3: ...ocks using solid or stranded wire sizes 0 5 2 5mm2 AWG 20 14 Wire insulation needs to be stripped 6 7mm Wires may be fitted securely with crimped ferrules Terminal screws need to be tightened down wit...

Page 4: ...kwise 7 Cable Routing and Tone Selection 7 1 Cable Routing Due to the compact design of the D2x units it is important that the user strips the outer sheath of and biases any cables over the size of 1m...

Page 5: ...ecting the alarm horn and strobe can be removed if the user wishes to power the strobe separately 9 4 Second Third and Fourth Stage Tone Selection For units set up for ve switching default setting Sta...

Page 6: ...cure the earth conductor to the earth stud The external earth conductor should be at least 4mm2 in size The external earth crimp ring should be located between the two M5 plain washers provided and se...

Page 7: ...www velocitydetection com Doc GLT 313 7 1 Issue 001 Date 28 10 2020 VL D2xC1X05 Explosion Proof Horn Alarm Strobe...

Page 8: ...www velocitydetection com Doc GLT 313 7 1 Issue 001 Date 28 10 2020 Tone Selection cont VL D2xC1X05 Explosion Proof Horn Alarm Strobe...

Reviews: