- 61 -
User Manual - CRONO.X programmable thermostat
English
ERROR MESSAGES
When there is a fault that prevents correct operation, e.g. failure of the temperature-
control sensor, the display
reads
“
---
” in place of the relevant temperature reading
(from internal or external sensor).
•
In case of sensor failure
when CRONO.X is in WINTER-HEATING mode,
the
relay will go on for 10 minutes every 4 hours to prevent the system from
freezing
•
In case of sensor failure
when CRONO.X is in
SUMMER/AIR-CONDITIONING
mode, the relay will stay permanently off
CONNECTION
8A / 250V~
NA NC COM
EXT NTC OUT BUS
Relay
output
The system control must be connected between the relay output contacts
COM
and
NA
.
The relay contact is potential free (clean contact).
The maximum contact capacity is 8A/250Vca
External sensor (EXT NTC)
An optional NTC temperature sensor
model X.TEMP
(code VN883500) can be
connected between terminals
EXT NTC
This sensor can be placed at a maximum distance of 40 m (use a shielded cable).
The X.TEMP sensor
can be used to read
the temperature in another room
or to
control the temperature
(only when SNS=YES and REG=EST).