2017.03
5 / 6
7. HANDLING & STORAGE
The fans are delivered on wooden pallets wrapped in plastic stretch. Transport the fan to the place of
assembly in its original packaging. During transport, connection cables, terminal box and wire connections
mustn’t be damaged. Load and unload the fan carefully, in order to avoid possible damage. Use suitable
lifting equipment. The fan should be stored in a safe, clean, dry, vibration free, location. A regular monthly
rapid spin of the impeller is recommended to prevent grease hardening and possible brinelling of the
bearings; the impeller should not be in the same angular position after rotation.
When dismantling the crate to gain access to the fan assembly care should be taken to avoid injury from
sharp edges, nails, staples, splinters, etc.
8. MAINTENANCE
Periodically check the screw connections, coil resistance, function of the safety components and control
elements. Only clean the fan manually, with a vacuum cleaner or with compressed air. Before service,
maintenance or repairing, disconnect the electrical connections and the impeller is stopped. The fan must be
cleaned when needed, at least once per year to maintain the capacity. The fan bearings are maintenance-
free and should be renewed only when necessary. Cleaning should be done without dislodging or damaging
the impeller. Make sure that there is no unexpected noise from the fan.
In addition to routine maintenance motor bearings will in the longer term require attention. If the motor
bearings are greased through extended lubricators, a quality of grease should be periodically applied in
accordance with the information on the fan or motor nameplate and/or instructions provided.
9. FAULT DETECTION
It is necessary to turn off the fan before checking the fan and the system. During maintenance, device
electrical connections should be cut entirely. All switches and circuit breakers should be locked by brought to
the OFF position. Also “DO NOT START” sign should be placed on the control panel that will consistently
stand.
Check that the electrical connections to the unit are secure. Check that the voltage applied at the fan
terminals is as specified on the motor nameplate, and is balanced. Measure the current on each phase (one
phase in the case of single-phase motors) of the motor in turn and check that the current consumption is
within the full load current specified on the motor nameplate.
Rotate the motor shaft by hand. Investigate any sound of grinding noises, internal chaffing, rubbing or
stiffness. Any observed defect may indicate that the bearings require lubrication or replacement. Ensure that
all fixings are secure. Make sure that the fan blade is not blocked by an object, if fan is still not working,
contact your supplier.
10. WARRANTY
The warranty period starts from the date of delivery and it is for 2 years. Including all parts of the
entire fan under warranty. The maximum repairing period is 30 business days. This period starts from
the date of notification to us. Fan's warranty does not include electrical connection errors, failures that
may arise due to voltage and user errors. The warranty is only valid under condition that the fan is
assembled, operated and periodic maintenance to be made according to this manual.
ALWAYS WEAR APPROPRIATE PROTECTIVE CLOTHING (INCLUDING HARD
HATS, EYE PROTECTORS A
ND EAR DEFENDERS) WHEN WORKİNG IN THE
VICINITY OF THE FAN ASSEMBLY