15. TROUBLESHOOTING
Table15.1. Troubleshooting Table
PROBLEM
INDICATIONS
POSSIBLE REASON
OTHER
REASONS
and
REMEDIES
NO AIR
FLOW
Motor is not
working
No current
No power
Check the power supply
Thermal protection is open
Fan motor cables at the
main controller board are not
tight
Control panel failure
Check the socket behind the
the controller
LOW AIR
FLOW
Pressure loss in the ducts are
higher than calculated
Check the duct design
Filters clogged or dirty
Clean filter or change it if
necessary
Too much leakage at the
pressure side of system
Filter doors are not closed or
duct connections are not
completed
Check the doors and duct
connections.
HIGH AIR
FLOW
Too much leakage at the
suction side of system
Duct connections are not
completed
Check the duct connections
Overcurrent of fan motors
Supply voltage is low
Engine is over loaded.
Measure the current taken
by engine.
Grills are not installed
Install the grills
Filters are not installed
Put the filters in