background image

5.6 I

NSTALLING

D

UAL

E

XTERIOR

H

OOD

(

CONT

D

)

5.6.3  C

ONNECTING

T

ANDEM

®

TRANSITION TO EXTERIOR

D

UAL

H

OOD

(

CONT

D

)

2.

Joint the end of the Tandem® transition to the rear of the exterior backplate. Secure 
with 2 Xmas tree pins and seal properly with duct tape.

3.

Lean the exterior backplate to the exterior wall. Using 4 #8 x 1 1/2” screws, fix it to the wall.
Seal the outline with caulking.

4.

Snap the assembled exterior hood on its backplate and secure with 2 provided screws
(#8 x 3/4” long).

5.7 C

ONNECTING THE

D

RAIN

(HRV 2500, HR 2.5, HEPA 3000 

AND

HF 3.0 

UNITS ONLY

)

VD0085

CAUTION

The exterior backplate must be installed with the word ‘’TOP’’ pointing upward.

Xmas tree pin

VD0086

VD0087

screw

5. INSTALL THE  UNIT 

(CONT’D)

VO0025

1

VO0046

1

2

3

2.

Hand tighten the 2 plastic 

drain fittings (

1

) using the 

gaskets (

2

) and nuts (

3

) as 

shown. Close the door.

VO0027

27'' 

686 mm

7''

(178 mm)

3.

Cut 2 sections of plastic tubing;

one 7’’ (178 mm) long and one 

27’’ (686 mm) long, and attach 

them to each drain fitting as 
shown.

VO0028

4.

Join these 2 sections to the 
‘’T’’ junction and main tube as 

shown.

VO0029

1

3

2

4

5

Tie-wrap

To drain

5

.Make a water trap loop in the tube to 

prevent the unit from drawing
unpleaseant odors from the drain
source. Make sure this loop is situated
BELOW the ‘’T’’ as shown. This will 
prevent water from being drawn back
up into the unit in case of negative 
pressure. Run the tube to the floor 
drain or an alternative drain pipe or
pail. Be sure there is a slight slope 
for the run-off.

- 17 -

1

.Remove the door by turning 

the switch knob to the OFF 
position (to unlock the door).

Then, unlatch the door and 

open it. Slide out the core
assembly to access the 2 
drain fitting hole locations (

1

).

Punch out the holes.

Summary of Contents for HEPA 3000

Page 1: ...OMEOWNER HOMEOWNER USE AND CARE INFORMATION ON PAGES 18 TO 20 READ AND SAVE THESE INSTRUCTIONS 04313 rev F M O D E L S VB0064 HEPA 3000 HF 3 0 HEPA 4000 HRV 2500 HR 2 5 Patents pending NOTES 1 HRV 250...

Page 2: ...et 4 Installation must be done in accordance with all applicable codes and standards including fire rated construction codes and standards 5 This unit is not designed to provide combustion and or dilu...

Page 3: ...HANG THE UNIT 11 5 3 PLANNING OF THE DUCTWORK 12 5 4 INSTALLING NON INSULATED DUCTS AND REGISTERS 12 5 4 1 STAND ALONE SYSTEM 12 13 5 4 2 CENTRAL DRAW POINT 13 14 5 4 3 RETURN TO RETURN 14 5 5 INSTALL...

Page 4: ...Fresh filtered air is supplied by the register located in the lowest liveable level See figure at right 1 1 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM VH0040 ALL UNITS For this type of ins...

Page 5: ...RRISBURG SACRAMENTO DENVER TOPEKA DETROI T INDIANAPOLIS SANTA FE SPRINGFIELD OKLAHOMA CITY PHOENI X COLUMBUS NASHVILLE ATLANTA BATON ROUGE AUSTIN COLUMBI A RALEIG H WASHINGTON HARTFORD BOSTON REN O HE...

Page 6: ...of the forced air unit To avoid cross contamination and achieve the highest efficiencies the forced air system blower must always be ON See figure below NOTE Home with multiple forced air systems shou...

Page 7: ...g the minimum clearance needed to open the door completely 22 5 15 75 572 mm 400 mm VD0117 VD0116 22 559 mm NOTE A minimum of 8 203 mm clearance from any obstruction on top of the unit is required for...

Page 8: ...ction installation only to cut ductwork Aluminum duct tape for plenum connection installation only Jig saw Caulking gun and caulking For HRV 2500 and HR 2 5 units the installation kit is 15273 For HEP...

Page 9: ...s the other end of the cable through the wall Reinstall the cover plate Using wall anchors and provided screws mount the wall control on the wall See illustrations below 1 Wall anchors 4 Control 1 Out...

Page 10: ...d front plate of the unit at this time they need to be removed for preparing the unit to be hung 2 When using the wall control the main switch on the unit must always be positioned to NORMAL REMOTE 6...

Page 11: ...ORTS ON THE UNIT Mount the 8 oval ports and the 5 to 6 oval ports on the top of the unit using the screws provided in the hardware box 4 screws 8 x 3 4 long per port See figure beside NOTE All ports o...

Page 12: ...e air circulation Keep in mind that the filtered air register must be located as far as possible from the stale air register If desired you can install another register sold separately Install the reg...

Page 13: ...ystem described in point 5 4 1 Fresh Filtered air ductwork Return side connection HRV 2500 AND HR 2 5 UNITS ONLY Locate the opening for fresh filtered air ductwork on the forced air unit at a minimum...

Page 14: ...1 1 3 AND 1 2 2 Fresh Filtered air ductwork Return side connection Same as for Central Draw Point described in point 5 4 2 Stale air ductwork Return side connection ALL UNITS Locate the stale air duc...

Page 15: ...the vapor barrier over the insulation 4 Apply duct tape gently to the joint in order to make an airtight seal See figures below Identify each insulated duct For fresh air from outside duct use the blu...

Page 16: ...exterior hood must be installed at a minimum distance of 18 inches 457 mm from the ground See illustration beside 5 6 3 CONNECTING TANDEM TRANSITION TO THE DUAL EXTERIOR HOOD 1 Using a jig saw cut a 6...

Page 17: ...the 2 plastic drain fittings 1 using the gaskets 2 and nuts 3 as shown Close the door VO0027 27 686 mm 7 178 mm 3 Cut 2 sections of plastic tubing one 7 178 mm long and one 27 686 mm long and attach...

Page 18: ...from a wood stove through out the house or the fresh air from a cooling system 6 CONTROLS OFF UNIT IS OFF AND DOOR IS UNLOCKED NORMAL REMOTE UNIT IS OPERATING ON NORMAL SPEED THIS IS THE RIGHT POSITI...

Page 19: ...cuum to remove most of the dust Let it soak in a solution of warm water and mild soap Rinse thoroughly and let dry before reinstalling it 5 Clean the inside walls of the unit with a clean damp cloth t...

Page 20: ...control for HV 2 5 and HF 3 0 units only All listed parts are available where you have bought your unit NOTE Please note that parts not listed are not available those parts require assembly knowledge...

Reviews: