40
Main Menu Buttons -
Settings
Installation Settings
(Continued)
Heat Pump Settings
Aux Heat Lockout Temp
(65
˚
)
HP Lockout Outdoor Temp
(65
˚
)
Heat Pump will not run below this temp. (0˚ - 75˚ F)
Aux Heat will not run above this temp. (0˚ - 75˚ F) GAS/EL or HP dip
switch must be set for HP and GAS or ELEC dip switch must be set for ELEC.
Aux Heat Lockout - DISABLED
Aux Heat Lockout - ENABLED
Turns on Aux Heat Lockout.
Heat Pump Lockout - DISABLED
Heat Pump Lockout - ENABLED
Turns on Heat Pump Lockout.
(Only available
when dip switch
is set for Heat
Pump operation.)
AUX Output Settings
AUX output usage
(W3)
Allows the W3/AUX output to be used for Heating, Humidification, or
Dehumidification.
IMPORTANT: Aux Output Usage must be set for Hum or Dehum
before any settings will take effect in the Humidity Main Menu.
AUX output polarity
(NO)
The AUX Output polarity may be set for
Normally Open or Normally Closed to
accommodate different types of
humidification and dehumidification
equipment.
A local outdoor
sensor connected
to the thermostat
is required.