23
Lockout Heat Pump on Outdoor Temp
(Setup Steps 55 - 56)*
This feature stops the heat pump from running below a specified outdoor temperature,
where the heat pump has become inefficient or could damage equipment. A local
outdoor sensor must be used for this feature to work.
Lockout Heat Pump With Outdoor Temp
(Setup Step 55)
When set to ON, the Heat Pump Lockout feature is enabled. When set to OFF, the
heat pump will stage normally.
Heat Pump Lockout Temp
(Setup Step 56)
This step allows the user to set the temperature at which the heat pump will be
locked out. Adjustable from 0 to 75 degrees Fahrenheit in five degree increments.
Auxiliary Heat Lockout
(Setup Steps 57 - 58)*
This feature allows the auxiliary heat for a heat pump (W2 and W3) to be locked out
above a specific outdoor temperature. These steps will only appear if the thermostat
jumper
J1
is set for
Heat Pump
and
J3
is set for
Electric Heat
. A local outdoor sensor
must be used for this feature to work.
Lockout Aux Heat With Outdoor Temp
(Setup Step 57)
When set to ON, the Aux Heat Lockout feature is enabled. When set to OFF, Auxiliary
Heat will stage normally.
Aux Heat Lockout Temp
(Setup Step 58)
(20˚ - 75˚) This step allows the user to set the temperature at which Auxiliary Heat
will be locked out. Adjustable from 20 to 75 degrees Fahrenheit.
NOTE: This temperature setting cannot be lower than 5 degrees above the Heat Pump
Lockout temperature.
Setup Steps
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.