25
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.
WARMER
COOLER
MODE
SETUP
Setup Steps
Smart Recovery
(Setup Step 65)
Smart Recovery turns on the heat or cool before the Morning start time to bring the room
temperature to the Morning setpoint at the start of the Morning time period. Please allow
4-8 days for Smart Recovery time to adjust. When used with a heat pump, electric strip
heat will be disabled while Smart Recovery is active.
Dry Contact Operation* (Setup Steps 66-67)
Dry Contact Polarity
(setup Step 66)
Open (Normally Open)
- The dry
contact is open until the connected
device closes the circuit.
Condensate Dry Contact Use
(Setup Step 67)
If selected when the dry contact is active, the thermostat will lockout the compressor
terminal(s) and “CONDENSATE PAN OVERFLOW” will appear on the display.
VACATION
- If VACATION is selected when the dry contact is active, the thermostat will
be forced into AWAY/unoccupied settings.
FDD
- If FDD is selected when the dry contact is active, the scrolling display will read
“Equipment fault”. This error message will disappear when the Dry Contact is idle.
Closed (Normally Closed)
- The dry
contact is closed until the connected
device opens the circuit.
Dr
y
Contact
‘Idle’
‘Active’
Dr
y
Contact
Dr
y
Contact
‘Idle’
‘Active’
Dr
y
Contact