Y2 JUMPER SETTING
If the jumper for MISC1 is set to Y2 the
second stage of cooling.
MISC1 screw terminal on the backplate will control a
Y2 OPERATION -
Page 14.4
Control up to two Cool stages.
The
2nd Stage
of heat or cool is turned on when:
(
A
) The 1st Stage has been on for the time required (
step #28,
page 14.6).
It is adjustable from 0-60 minutes and the default
is two minutes.
(
B
) The temperature spread from the setpoint is equal to or greater
than:
the setpoint plus the deadband (step #25, page 14.5), plus
the 2nd deadband (step #26, page 14.5).
This 2nd deadband is
adjustable from 0-10 degrees and the default is two degrees.
Page 21.5
Explanation of Jumper Settings
(continued)
And
21
Cool
Setpoint
Deadband
Deadband
db 1
db 2
(adj. 0-10 )
(adj. 1-6 )
1st Stage
turn on
2nd Stage
turn on
Cooling
TEMPERATURE
INCREASE