SINGLE SETPOINT BEHAVIOR - When configured
for
Single Setpoint
operation
(step #4, page 19)
,
the
degree icon will blink when the large number is display-
ing room temperature and will remain solid when dis-
playing the heating or cooling setpoint. In the Auto and
Program On modes the deadband is enforced both
above and below the setpoint. To avoid short cycling,
a deadband of at least two degrees is recommended
(step #9, page 20)
. To display the room temperature
press and hold the MODE button for two seconds.
Release the MODE button to return to the normal
display.
Page 33
FAN COIL TYPE - This step instructs the thermostat
how to set the G, G2, and G3 outputs to yield the
desired fan speeds. Since this a low voltage
thermostat, the fan coil should have multiple relays or
contactors to supply the voltages needed for the fan
motor. Most fan coils will have 3 relays and require
only one relay to be driven at a time. However,
many models of Carrier or IEC fan coils contain a
relay board with special logic that requires different
output settings from the thermostat. If there is any
question, please contact the fan coil manufacturer.
Step 8 = OFF
Step 8 = ON
Speed
LO
MED
HI
Speed
LO
MED
HI
G
ON
G
ON
ON
ON
G2
ON
G2
ON
G3
ON
G3
ON