29
Installer Setup
Setpoint Limits
(setup step 22)
When this feature is set to ON, the heat and cool setpoints can be restricted to
preset levels, set in steps 19 and 20.
Maximum Heat Setpoint (Setup Step 23) - (35˚ - 99˚).
Minimum Cool Setpoint (Setup Step 24) - (35˚ - 99˚).
Cycles Per Hour
(setup step 25)
The Cycles Per Hour setting may limit the number of times per hour your
HVAC unit may energize. For example, at a setting of 6 cycles per hour the
HVAC unit will only be allowed to energize once every 10 minutes. The Cycles
Per Hour limit may be overridden and reset by pressing the WARMER or
COOLER buttons on the thermostat. Settings are No Limit, 2, 3, 4, 5, or 6.
Compressor Minimum Off Minutes
(setup step 26)
This feature allows the user to set a minimum off time for the compressor.
Settings are 5 mins., 3 mins., or 0 mins.
Minimum Heat/Cool Setpoint Difference
(setup step 27)
This feature allows the user to set the minimum gap between Heat and Cool
setpoints in AUTO mode. Select from 0 to 6. If setup step 2 is not set for
AUTO-CHANGEOVER, this step will not appear.
Number of Heat Stages (Setup Step 28)
Number of Cool Stages (Setup Step 29)
Number of Aux Heat Stages (Setup Step 31)
Number of Compressor Stages
(setup step 30)
This feature is for heat pump application only.
This feature allows the thermostat to control 1 or 2 compressor stages when
configured for heat pump.
NOTE: When step 59 (Dual Fuel) is set to ON, this step will not appear and
Compressor Stages will automatically be set to 2.