35
Installer Setup
Auxiliary Output
The Voyager Thermostat is equipped with a programmable auxiliary output.
This output can be configured to be controlled from a variety of sources.
Aux Output Polarity
(setup step 65)
Specifies if the Auxiliary output will be Open (Normally Open) or Closed
(Normally Closed).
Aux Output
(setup step 66)
Specifies which source will control the Aux output.
Choices are:
Time - Uses the internal clock of the thermostat.
Temp - Uses one of three temperature sources.
External - The Auxiliary Output is controlled from an external accessory source.
Error - Uses the thermostat’s error processing to signal an active error condition.
Free Cooling - Drives a damper to bring fresh air in from outdoors.
Venting - Drives a damper to exhaust inside air to the outside.
Auxiliary Output Programming By Time
If TIME is selected for the Aux Output, the following setup steps will appear:
Aux Output Days (Setup Step 67) - Specifies if the Aux Output will be single day
(1 DAY), weekday/weekend (5/2 DAY), or seven day (7 DAY) programmable.
Day Of Week To Program (Setup Step 68) - Specifies which day of week to
program.
Aux Output Start Time (Setup Step 69) - Specifies the time of each day when the
Aux output will turn on.
Aux Output Stop Time (Setup Step 70) - Specifies the time of each day when the
Aux output will turn off.
Copy (Setup Step 71) - This step only appears if Aux Output Days (setup step 63)
is set for 7 programmable output days.