40
Technician Setup
Hold for 10 seconds
All icons appear
Press MODE to advance
through the setup steps
Press WARMER or COOLER
to adjust the selection
WARMER
COOLER
MODE
SETUP
HI
Lo
Program ONOFF
Outdoor
Fan On
C
OO
L
A
UX
H
EAT
Day Night
Morning
Evening
Setup Step
2nd3rd
Stage
Am
Pm
18:88
188
188
88
188
Morning Day Night
Evening
To enter Technician Setup, press and hold the SETUP button for 10 seconds.
After all the icons appear, press MODE. The version number of the thermostat
will appear in the scrolling text. Press MODE to advance to the next step.
Use the WARMER or COOLER buttons to adjust the value of your selection.
To leave Technician Setup, press SETUP.
Technician Setup is for diagnostic and testing purposes and is intended for
use by a qualified technician. See page 15 for more detailed instructions.
Technician Setup contains the following options:
• View the version number of the thermostat.
• View the jumper setting of J1 (Gas/Electric or Heat Pump), J2 (Reversing
Valve: RV=O or RV=B), and J3 (Fan: Gas or Electric) jumpers located on the
back of the thermostat. (Remove thermostat from backplate for access)
• View the state of the Dry Contact and Fault terminals.
• Turn on equipment outputs for testing.
• Calibrate thermostat, remote, and humidity sensors.
• Control HUM output (On or Off)
• Control DEHUM output (On or Off)
• Control AUX output (On or Off)