42
Advanced Setup Table
Df = Factory Default Setting
Step# Description
Pg# Range
Df
34
3rd Stage Deadband
30 0 - 10 Degrees
2
35
4th Stage Deadband
30 0 - 10 Degrees
2
36
Minutes Between 1st and 2nd Stage 30 0 - 60 Minutes
2
37
Minutes Between 2nd and 3rd Stage 30 0 - 60 Minutes
2
38
Minutes Between 3rd and 4th Stage 30 0 - 60 Minutes
2
39
2nd StageTurnoff Point
30 Deadband, Setpoint
Deadband
40
3rd StageTurnoff Point
30 Deadband, Setpoint
Deadband
41
4th Stage Turnoff Point
30 Deadband, Setpoint
Deadband
42
Fan Program
31 On, Off
Off
43
Minutes of Fan Runtime
31 0-60
0
44
Fan Program Start Time
31 12:00A - 12:00A
7:00A
45
Fan Program Stop Time
31 12:00A - 12:00A
7:00A
46
Wired Sensor Type
8
Remote, Supply
Remote
47
Control to Temp Source
34
Thermostat, Remote, Average
Thermostat
48
Humidity Only With Heat
32 On, Off
Off
49
Fan With Humidity Demand
32 Fan On, Fan Off
Fan Off
50
Fan With Dehumidify Demand
32 Fan On, Fan Off
Fan Off
51
Humidity Setpoints
32 Auto, Manual
Manual
52
Cool To Dehumidify
32 On, Off
Off
53
Maximum Dehum Overcool
32 0 - 20 Degrees
2
54
Reheat Operation W/Cool To Dehum. 32 On, Off
Off
55
Lockout Heatpump with Outdoor Temp
33 On, Off
Off
56
Lockout Temp
33 0 - 75 Degrees
35
57
Lockout Aux Heat w/Outdoor Temp
33 On, Off
Off
58
Aux Heat Lockout Temp
33 20 - 75 Degrees
75
59
Dualfuel
33 On, Off
Off
60
Dualfuel Changeover on Outdoor Temp
34 On, Off
Off
61
Dualfuel Balance Point
34 0 - 60 Degrees
35
62
Dualfuel Changeover Delay in Seconds
34 0 - 90 Seconds
30
63
Fan Off Delay
31 0 - 120 Seconds
0
64
F/C
34 Fahrenheit (F), Celsius (C) F
65
Aux Output Polarity
35 Open, Closed
Open
66
Aux Output
35 Time, Temp, External,
Time
Free Cooling, Venting
67
Aux Output Program Days
35 1 Day, 5/2 Day, 7 Day
1
68
Day Of Week To Program
35 Sunday - Monday (S - M)
MTWTFSS
69
Aux Output Start Time
35 12am - 12am
7am
70
Aux Output Stop Time
35 12am - 12am
9pm
71
Copy
35 Yes, No
No
72
Aux Output Temp Source
36
Stat, Outdoor, Remote, External
Remote
cont. next page