24
Setup Steps
Second Stage on Turnoff Point (Setup Step 38) -
Specifies whether second stage
will turn off at first stage deadband or remain on until the room temperature demand
is satisfied. Choose between Deadband or Setpoint.
Third Stage Turnoff Point (Setup Step 39) -
Specifies whether third stage will turn
off at second stage deadband or remain on until the room temperature demand is
satisfied. Choose between Deadband or Setpoint.
Fourth Stage Turnoff Point (Setup Step 40) -
Specifies whether fourth stage will
turn off at third stage deadband or remain on until the room temperature demand is
satisfied. Choose between Deadband or Setpoint.
Minutes of Fan Purge*
(setup step 41)
When this feature is activated, the fan will turn on during an unoccupied period at a
preset amount of time prior to Occupied 1. This preoccupancy fan purge timer may be set
from zero to three hours, in 15 minute increments. Zero means this feature is turned off.
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.
WARMER
COOLER
MODE
SETUP