48
Advanced Setup Table
cont. next page
Df = Factory Default Setting
Step# Description
Pg# Range
Df
1
Available Modes
17
Heat/Cool/Auto/Off, Heat/Cool/Off, Heat/Cool/
Heat/Off, Cool/Off
Auto/Off
2
Backlight
18
On, Off
Off
3
Backlight Level
18
Off through 7 levels of brightness Level 5
4
Night Dimmer
18
On/Off
Off
5
Night Dimmer Brightness
18
Off through 7 levels of brightness 2 (20%)
6
Night Dimmer Start Time
18
12A-12A
8:00P
7
Night Dimmer Stop Time
18
12A-12A
6:00A
8
Current Service Filter Runtime Hours
18
0-1999 Hours
0
9
Current Service Filter Calendar Days
18
0-720 Days
0
10
Current Heat Runtime Hours
19
0-1999 Hours
0
11
Current Aux Heat Runtime Hours
19
0-1999 Hours
0
12
Current Cool Runtime Hours
19
0-1999 Hours
0
13
Current Override Hours
19
0-1999 Hours
0
14
Current UV Lamp Calendar Days
19
0-720 Days
0
15
Current Humidifier Calendar Days
19
0-720 Days
0
16
Set Service Filter Runtime Hours
20
0-1950 hours
0
17
Set Service Filter Calendar Days
20
0-720 Days
0
18
Set UV Lamp Calendar Days
20
0-720 Days
0
19
Set Humidifier Calendar Days
20
0-720 Days
0
20
Language
20
English, Espanol, Francais
English
21
Setpoint Limits
21
0 - 3
0
22
Max Heat Setpoint
21
35 - 99 Degrees
74
23
Min Cool Setpoint
21
35 - 99 Degrees
70
24
Cycles Per Hour
22
No Limit, 2, 3, 4, 5, 6
6
25
Compressor Minimum Off Minutes
22
0,3,5
5
26
Min. Heat/Cool Setpoint Difference
22
0 - 6 Degrees
2
27
Number of Heat Stages
22
0 - 3
2
28
Number of Cool Stages
22
0 - 2
1
29
Number Of Compressor Stages
22
1, 2
1
30
Number of Auxiliary Stages
22
0, 1, 2
0
31
1st Stage Deadband
23
1 - 6 Degrees
2
32
2nd Stage Deadband
23
0 - 10 Degrees
2
33
3rd Stage Deadband
23
0 - 10 Degrees
2
34
4th Stage Deadband
23
0 - 10 Degrees
2
35
Minutes Between 1st and 2nd Stage
23
0 - 60 Minutes
2
36
Minutes Between 2nd and 3rd Stage
23
0 - 60 Minutes
2
37
Minutes Between 3rd and 4th Stage
23
0 - 60 Minutes
2
38
2nd StageTurnoff Point
24
Deadband, Setpoint
Deadband
39
3rd StageTurnoff Point
24
Deadband, Setpoint
Deadband