24
Setup Steps
Second Stage Turnoff Point (Setup Step 35) -
Specifies whether second stage will
turn off at first stage deadband or remain on until the room temperature demand is
satisfied. Choose between Deadband or Setpoint.
Third Stage Turnoff Point (Setup Step 36) -
Specifies whether third stage
of cooling will turn off at second stage deadband or remain on until the room
temperature demand is satisfied. Choose between Deadband or Setpoint.
Fourth Stage Turnoff Point (Setup Step 37) -
Specifies whether fourth stage of
cooling will turn off at third stage deadband or remain on until the room temperature
demand is satisfied. Choose between Deadband or Setpoint.
Minutes of Fan Purge*
(setup step 38)
When this feature is activated, the fan will turn on during an unoccupied period at a
preset amount of time prior to Occupied 1. This preoccupancy fan purge timer may be set
from zero to three hours, in 15 minute increments. Zero means this feature is turned off.
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.
WARMER
COOLER
MODE
SETUP