32
Setup Steps
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.
WARMER
COOLER
MODE
SETUP
IAQ Air Patrol (Setup Step 66)
Select whether you want the Air Patrol features to be ENABLED or DISABLED. You may
always view the IAQ value regardless of this setting.
Air Patrol on if IAQ exceeds MODERATE Quality (
Setup Step 67)
This setting specifies at which IAQ category that Air Patrol actives, either MODERATE or
POOR. This step only appears if Step #66 is set to ENABLED.
Air Patrol Fan on Minutes (Setup Step 68)
When IAQ value meets the level specified in Step #67, the indoor blower will run for the
length of time specified in this step, 5 to 60 minutes. This step only appears if step #66
is set to enabled.
Skyport* (Setup Step 69)
Set to ON to allow access to Skyport services or to OFF to not allow access to Skyport
services. Visit venstar.com for more information.
Local API* (Setup Step 70)
Set to ON to allow third-party software to interface with your thermostat. Typically used
with home automation set-ups.
Show Clock (Setup Step 71)
Select ON or OFF to have the time of day appear on the screen
Show IAQ
(Setup Step 72)
Select ON or OFF to have IAQ measured levels of MODERATE or POOR show on the
scrolling display.
Press Fan To Clear All Messages (Setup Step 73)
This feature allows the user to clear all current error messages from the display.