47
29
2nd Stage Deadband
23
0 - 10 Degrees
2
30
3rd Stage Deadband
23
0 - 10 Degrees
2
31
4th Stage Deadband
23
0 - 10 Degrees
2
32
Minutes Between 1st and 2nd Stage
23
0 - 60 Minutes
2
33
Minutes Between 2nd and 3rd Stage
23
0 - 60 Minutes
2
34
Minutes Between 3rd and 4th Stage
23
0 - 60 Minutes
2
35
2nd StageTurnoff Point
24
Deadband, Setpoint
Deadband
36
3rd StageTurnoff Point
24
Deadband, Setpoint
Deadband
37
4th Stage Turnoff Point
24
Deadband, Setpoint
Deadband
38
Minutes of Fan Purge
24
0 - 3:00, 15 min. increments - 0 = off
0
39
Wired Sensor Type
25
Remote, Supply, Return
Remote
40
Control to Temp Source
25
Thermostat, Wired Remote*, Wireless
Remote, Average of Wireless
Remotes, Average Thermostat and
Wired Remote*, Average All Sensors.
*Option only if prior step = “Remote”
Thermostat
41
Wireless Remote to Use
25
list of wifi sensors currently linked to
thermostat. * This step only appears
if prior step = “Wireless Remote”
first linked
sensor
in list
42
Humidity Only With Heat
26
On, Off
Off
43
Fan With Humidify
26
Fan On, Fan Off
Fan Off
44
Fan With Dehumidify
26
Fan On, Fan Off
Fan Off
45
Cool To Dehumidify
26
On, Off
Off
46
Maximum Occ Dehum Overcool
26
0 - 20 Degrees
2
47
Maximum Unocc Dehum Overcool
26
0 - 20 Degrees
2
48
Fan Off Delay
26
0 - 120 Seconds
0
49
F/C
27
Fahrenheit (F), Celsius ©
F
50
Smart Recovery
27
On, Off
Off
51
Dry Contact Polarity
28
Open, Closed
Open
52
Dry Contact Use
28
Occupied,Condensate Pan, FDD,
Holiday,Doorswitch
Occupied
Advanced Setup Table
Df = Factory Default Setting
Step# Description
Pg# Range
Df
cont. next page