32
Installer Setup
Dry Contact Operation
(setup step 64 - 65)
Dry Contact Polarity (setup step 64)
Open (Normally Open) - The dry
contact is open until the connected
device closes the circuit.
Dry Contact Use (setup step 65)
CONDENSATE - If CONDENSATE is selected when the dry contact is active, the
thermostat will lockout the compressor terminal(s) and “CONDENSATE PAN
OVERFLOW” will appear on the display.
OCCUPIED - If OCCUPIED is selected when the dry contact is active, the
thermostat will be forced into Occupied 1. This setting may be used with time
clocks or twist timers to force the thermostat from Occupied to Unoccupied, or
from Unoccupied to Occupied depending on the dry contact polarity.
FDD - If FDD is selected when the dry contact is active, “EQUIPMENT FAULT”
will appear on the display.
HOLIDAY - The Holiday feature allows the thermostat to use temporary, energy
saving settings without having to change regular programming. Holiday
setup/programming at the local thermostat is limited to the number of days
employing Holiday settings. When the optional Wi-Fi module is detected in the
thermostat, local Holiday programming at the thermostat of the Holiday setup
is not allowed. In this case Holiday setup and programming is accomplished
with the Skyport Web App. Skyport gives the user extensive control over
Holiday settings.
Press the Holiday button to enter Holiday programming (no Wi-Fi Module
detected).
If there is not a Holiday period active:
Use the Warmer and Cooler buttons to choose the number of days desired to
run the Holiday feature. To confirm your settings and advance to the next step,
press the Holiday button again. Choose the desired Holiday Cool set point.
Press Holiday. Then choose the desired Holiday Heat set point. Press Holiday
to return to the main screen.
Closed (Normally Closed) - The dry
contact is closed until the connected
device opens the circuit.
Dr
y
Contact
‘Idle’
‘Active’
Dr
y
Contact
Dr
y
Contact
‘Idle’
‘Active’
Dr
y
Contact