40
Advanced Setup Table
Default = Factory Default Setting
Step# Description
Pg# Range
Default
36
4th Stage Deadband
29 0 - 10 Degrees
2
37
Minutes Between 1st and 2nd Stage 29 0 - 60 Minutes
2
38
Minutes Between 2nd and 3rd Stage 29 0 - 60 Minutes
2
39
Minutes Between 3rd and 4th Stage 29 0 - 60 Minutes
2
40
2nd StageTurnoff Point
29 Deadband, Setpoint
Deadband
41
3rd StageTurnoff Point
29 Deadband, Setpoint
Deadband
42
4th Stage Turnoff Point
29 Deadband, Setpoint
Deadband
43
Minutes of Fan Purge
30 0 - 3:00, 15 min.
0
increments - 0 = off
44
Wired Sensor Type
8
Remote, Supply
Remote
45
Control to Temp Source
32 Tstat, Remote, Average
Tstat
46
Humidity Only With Heat
31 On, Off
Off
47
Fan With Humidity Demand
31 Fan On, Fan Off
Fan Off
48
Fan With Dehumidify Demand
31 Fan On, Fan Off
Fan Off
49
Cool To Dehumidify
31 On, Off
Off
50
Maximum Dehum Overcool
31 0 - 20 Degrees
2
51
Reheat Operation W/Cool To Dehum. 31 On, Off
Off
52
Fan Off Delay
30 0 - 120 Seconds
0
53
F/C
32 Fahrenheit (F), Celsius (C) F
54
Aux Output Polarity
33 Open, Closed
Open
55
Aux Output
33
Time, Temperature,
External, Economizer, Y4
Time
56
Aux Output Program Days
33 1 Day, 5/1/1 Day, 7 Day
1
57
Day Of Week To Program
33 Sunday - Monday (S - M)
MTWTFSS
58
Aux Output Start Time
33 12am - 12am
7am
59
Aux Output Stop Time
33 12am - 12am
9pm
60
Copy
33 Yes, No
No
61
Aux Output Temp Source
34
Tstat, Outdoor, Remote, Ext.
Remote
62
Aux Output Trigger Point Temp
34 0 - 120 Degrees
65
63
Comfort Recovery
30 On, Off
Off
64
Dry Contact Polarity
32 Open, Closed
Open
65
Dry Contact Use
32
Cond. Pan, Occupied, FDD, Holiday
66
Humidity Polarity
31 Open, Closed
Open
67
Dehumidify Polarity
31 Open, Closed
Open
68
Dehumidify only with Cooling
31 On, Off
On
69
Light Activation Sensitivity
32 Press Fan button to set
current light level
70
Light Activation to Occupied
32 On/Off
Off
71
Skyport
21 On, Off
On
72
Local API
23 On, Off
Off
73
Press Fan To Clear All Messages
34