background image

Page 5

JPH/C1 1213A

Installation Details Continued

7)  Install an appropriate 1/2" UL listed electrical wire clamp through each motor box electrical opening on top of the hood. 

Install electrical wiring from the service panel to the hood location for each motor box. Consult the connection diagrams 

(on previous page) for further details on electrical placement. Extend wiring to the hood. Electrical connection(s) will 

occur before the hood is installed on the wall.

8)  Lift the hood to the location on the wall where it will be installed. Lightly mark the wall with a short, horizontal mark 

along the bottom edge of the hood. When finished, remove the hood from the wall.

9)  On the back side of the hood, measure the distance between the bottom edge of the hood and the top edge of the 

wood mounting strip. Measure this distance above the horizontal mark made in Step 8 and lightly mark the wall with 

a level, horizontal line. Measure where the center (left to right) of the hood will be and mark the upper, horizontal line 

on the wall with a short, vertical centerline.

10) Remove the screws inside the top of the back of the hood that retain the wood strip that is recessed in the mounting 

channel. Note: Some retaining screws may be located behind the blower(s). Remove the wood mounting strip from 

the back of the hood and place the top edge of the strip on the upper, level, horizontal line on the wall. Referencing the 

vertical centerline from Step 9, place the mounting strip on the wall so it is centered (left to right) in the space where 

the hood will be located. Drill pilot holes in the strip to prevent splitting. Using proper hardware, attach the mounting 

strip to at least two wall studs.

Model

Volts

Amps*

Hz

RPM

CFM

SP@0.0" Equivalent CFM

CFM

SP@0.1"

CFM

SP@0.2"

CFM

SP@0.3"

Minimum Round

Duct Size

Sones

#

B100 Single

115

1.5

60

1550

300

450

273

245

225

6" (28 in.

2

)

5.4

B200 Dual

115

2.9

60

1550

600

900

531

480

430

8" (50 in.

2

)

6.5

B200 Dual & B100 Single

115

4.4

60

1550

900

1350

804

725

655

VP562: 10" (79 in.

2

)

6.3

Two B200 Duals

115

5.8

60

1550

1200

1800

1062

960

860

VP563: 12" (113 in.

2

)

6.6

*  Add 2.5 amps for each warming light and 0.5 amp for each halogen light.

•  Because the Magic Lung

®

 blower uses centrifugal filtration rather than conventional baffle or mesh filters, the Magic Lung

®

 blower can handle cooking equipment with higher cubic feet per minute (CFM) requirements and can deliver equivalent CFM much more 

efficiently than other than other filtration systems. When comparing the Magic Lung

®

 with other blower units made by other manufacturers, use the “Equivalent CFM”.

#

  Ratings in accordance with the Standard Test Code by the Energy Systems Laboratory of the Texas Engineering Experiment Station.

4)  Remove the hood from its packaging and place the back of the hood on the floor or countertop in front of the wall 

where it will hang.

5)  Remove the shipping tape that is securing the E-Z Clean shield(s) inside the hood. Remove the E-Z Clean shield(s) by 

lightly pulling it toward the front of the hood. Gently close the back draft damper(s) from the top side of the hood. To 

remove the blower housing(s), unsnap the suitcase latches (one on each side of the housing). The housing(s) should 

be pulled forward and gently “tipped” to clear the blower wheel(s) and then out of the hood.

Warning:  Make sure power is off and locked at the service disconnecting 

means on the service panel during installation.

6)  Remove the three screws retaining the blower motor(s). Unplug 

and remove the motor(s), taking care not to damage the blower 

wheel(s). It is not necessary to remove the blower wheel from 

the motor.

Summary of Contents for JPH/C1 DESIGNER series

Page 1: ...lling into wall or ceiling do not damage electrical wiring and other hidden utilities C Ducted fans must always be vented to the outdoors D Sufficient air is needed for proper combustion and exhaustin...

Page 2: ...00 B200 10 round or equivalent 79 sq in VP562 Optional Two Duals Two B200s 12 round or equivalent 113 sq in VP563 Optional Ducting Requirements NEVER reduce the duct size When combining ducts together...

Page 3: ...he duct s should extend 1 below the ceiling Use duct tape to seal all joints A complete listing of available Vent A Hood ducting materials is provided on the back page of this instruction sheet Transi...

Page 4: ...6 1 11 11 5 5 Wall Side 5 1 Electrical 2 8 Outlet Vent Holes 8 Outlet Centerline of Hood Installation Details Continued Connection Diagram 36 48 Widths 300 CFM B100 Single Blower Top View 600 CFM B200...

Page 5: ...l Volts Amps Hz RPM CFM SP 0 0 Equivalent CFM CFM SP 0 1 CFM SP 0 2 CFM SP 0 3 Minimum Round Duct Size Sones B100 Single 115 1 5 60 1550 300 450 273 245 225 6 28 in 2 5 4 B200 Dual 115 2 9 60 1550 600...

Page 6: ...previously removed from the strip in Step 10 into the pilot holes drilled in Step 12 SKIP STEP 14 PROCEED DIRECTLY TO STEP 15 14 If applicable install the transition on the insides of the exhaust col...

Page 7: ...23 VP563 30 3 x 10 TO 7 TRANSITION MODEL DIM VP521 3 x 10 to 7 7 7 3 10 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 6 VP539 VP540 VP541 6 Round 7 Round 8 Round 16 16 LOW PROFILE ROOF JACK MAXI...

Reviews: