background image

 

INSTALLATION 

 

Position the unit, taking into consideration the position of the rooms to be ventilated, the exhaust position 
and the electrical services. Ensure there is adequate access for installation and maintenance. The unit can 
be mounted horizontally or vertically. It can be positioned on the floor, wall or ceiling. 
 
If the unit is sited in the heated void of the dwelling a condensate drain should not be necessary. 
When sited in a cold void, consideration should be given to fitment of a condensate drain. Alternatively the 
unit and ducting can be externally insulated to minimize condensation within the units housing. 
To reduce the system resistance in your duct system, and thereby avoid an increase in speed, power 
consumption and sound of the fan, follow these guidelines: 

 

1.1.  Keep the length of duct runs to a minimum, particularly the exhaust duct run. 
1.2.  If you need to use flexible ducting, make sure that it is fully extended and not crushed, 

sagging or torn. 

1.3.  Try to minimize the systems pressure drop by designing for lower in-duct velocities and connect to 

the rooms with low pressure drop ceiling valves. 

1.4.  The bend radius (measured to the inside of the bend), should be at least 1x the duct diameter.  
1.5.  Avoid having any bends, filters or other obstructions within 250mm of the fan inlets and outlet. 
1.6.  Set the valves to their maximally opened positions for a minimal pressure drop. 

 
Securely mount the unit through the mounting holes on the casing using appropriate fixings for the 
mounting substrate. Anti-vibration mounts; acoustic mat or rubber bushes can also be used. 
 
Fixings (not supplied) must be capable of securing 4 x the weight of the unit. Unit weight: 4.1kg 

 
 
To maintain the Ingress Protection (IPx2) rating of the unit, the unit must NOT be mounted with the 
cover removal slots facing upwards, or at an angle where they are visible from above. 
All other orientations are acceptable. Do not mount the unit with the outlet duct pointing down. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
See the dimensional details below for the mounting hole positions. 
Spigots are 125mm diameter. 125 

– 150mm accessory adaptors are available. 

 
 
 
 
 
When installing Ø90mm ducting onto a Unif unit, keep inserting the  
ducting into the sockets until three clicks have been heard. 
Full insertion of the ducting is necessary to achieve a  
seal with the unit. 
 

 

Cover removal slots. 

Figure 3 

Figure 4 

Summary of Contents for 1003000074

Page 1: ...z MULTIHOME RANGE VENTILATION SYSTEMS Installation and Wiring Instructions Basic NL 8000001174 Wireless NL 8000001175 Basic Perilex NL 8000001176 Basic Perilex CO2 NL 8000001260 Wireless Perilex NL 80...

Page 2: ...ible for their safety Young children should be supervised to ensure that they do not play with the appliance Cleaning and user maintenance shall not be done by children The installer is responsible fo...

Page 3: ...es Yes No Yes Yes Multihome Basic Perilex NL 4 300 Yes No Yes Yes No No No Multihome Basic Perilex CO2 NL 4 300 Yes No Yes Yes Yes No No Multihome Wireless Perilex NL 4 368 Yes Yes Yes Yes No Yes Yes...

Page 4: ...8000001177 Wireless Perilex CO2 NL 8000001261 Wireless BE 1003000074 Uniflexplus Wireless BE 1003000075 Wireless CO2 BE 1003000077 Uniflexplus Wireless CO2 BE 1003000078 Basic NL 8000001174 Basic Per...

Page 5: ...the rooms with low pressure drop ceiling valves 1 4 The bend radius measured to the inside of the bend should be at least 1x the duct diameter 1 5 Avoid having any bends filters or other obstructions...

Page 6: ...6 Figure 5 Figure 6...

Page 7: ...ducting radiating out horizontally ii Vertically mounted Installation with the exhaust spigot at top The electrical connections must come out of the bottom of the unit in order to maintain the water i...

Page 8: ...t When commissioning the unit a delay on timer and an overrun timer can be selected and adjusted in the software using the buttons and screen See Unit Adjustment section on page 12 of this document fo...

Page 9: ...jumper or dedicated neutral connection This appliance incorporates an earth connection for functional purposes only Connection Description 1 L Live 220 240Vac 2 N Neutral 3 Functional Earth 4 LS1 Live...

Page 10: ...input 1 I D OUT 2 COM Digital output common Unpowered Boost indicator Switch switching 6V 50mA max J Digital output 2 K D OUT 1 COM Digital output common Unpowered LED fault indicator switch switchin...

Page 11: ...red devices is displayed on the unit Removing sensors To remove paired sensors the unit must be reset Caution this will reset all values back to factory default Press the Mode button to turn on the di...

Page 12: ...g If a rapid rise is detected the fan will boost until the humidity lowers again Humidity Ambient response When ambient response is enabled the threshold set point is modified based on the ambient tem...

Page 13: ...Low Normal Boost Purge I e Boost is always higher than Normal 6 The actions for each of the Live Switched LS inputs are selectable The setting for delays and over run timers are applicable to all inpu...

Page 14: ...action Low Normal Boost or Purge speed Low A1HA Analogue 1 high action Low Normal Boost or Purge speed Boost A1tL Analogue 1 low threshold Analogue Input Threshold Low 1 99 15 A1tH Analogue 1 high th...

Page 15: ...tartup check Turn the power off and on again F02 Motor Fault No RPM Check that the impellor has free movement Check internal motor wiring F03 Humidity Temp sensor Fault No value internal sensor Contac...

Page 16: ...lared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Ducted BVUs not intend...

Page 17: ...ontrol Factor CTRL 0 65 Control Typology Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVU...

Page 18: ...CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your original supplier or nearest Vent Axia Centre by post or personal visit Please ensure that it is adequately...

Page 19: ...E MULTIHOME SYST MES DE VENTILATION Instructions d installation et de c blage Basic EP NL 8000001425 Basic Perilex C NL 8000001426 Basic Perilex D NL 8000001427 Economic EP NL 8000001428 Economic Peri...

Page 20: ...ppareil n est pas con u pour tre utilis par des personnes enfants inclus aux capacit s physiques sensorielles ou mentales r duites ou ne disposant pas de l exp rience ou des connaissances requises moi...

Page 21: ...enu le certificat RED n 0051 RED 0011 REV 0 Zirconium sans fil 14 dBm EIRP 868 mHz nominal Le fabricant garantit par la pr sente que ce type d quipement radio Bluetooth et radio 868 mHz est conforme l...

Page 22: ...Multihome BEP BPC BPD NL 4 300 Oui Non Oui Oui Non Oui Non Multihome EEP EPC EPD NL 4 368 Oui Non Oui Oui Non Oui Non Multihome AEP NL 4 368 Oui Oui Oui Oui Non Oui Oui Multihome AEC NL 4 368 Oui Oui...

Page 23: ...2 NL 8000001177 EPD NL 8000001430 EPC NL 8000001429 EEP NL 8000001428 Wireless BE 1003000074 Uniflexplus Wireless BE 1003000075 Wireless CO2 BE 1003000077 Uniflexplus Wireless CO2 BE 1003000078 BEP NL...

Page 24: ...ng et qu il n est pas cras affaiss ni rompu 1 9 Essayez de minimiser la chute de pression dans le syst me en tenant compte lors de la conception des conduits et en utilisant des bouches basse pression...

Page 25: ...es manchons 125 mm Adaptateurs auxiliaires de 125 150 mm disponibles Lors de l installation du conduit 90 mm dans un appareil Uniflexplus maintenez le conduit ins r dans les manchons jusqu entendre tr...

Page 26: ...26 Figure 7...

Page 27: ...rtant l horizontale v Installation mont e la verticale le manchon d vacuation se trouvant sur le dessus Afin de maintenir la protection contre l infiltration d eau il faut que les raccordements lectri...

Page 28: ...orisation et un d lai de d passement du temps accord et les r gler dans le logiciel l aide des touches et de l cran Pour des renseignements d taill s reportez vous au paragraphe R glage de l appareil...

Page 29: ...en d un c ble cavalier ou d une connexion neutre d di e Cet appareil incorpore une prise de terre des fins fonctionnelles uniquement Connexion Description 1 L Phase 220 240 V c a 2 N Neutre 3 Terre fo...

Page 30: ...rique commune T moin lumineux Survitesse sans tension commutation 6 V 50 mA max J Sortie num rique 2 K D OUT 1 COM Sortie num rique commune T moin lumineux d faut LED sans tension commutation 6 V 50 m...

Page 31: ...plusieurs capteurs Activez la fonction Appariement du capteur apparier reportez vous la notice d instructions qui accompagne le capteur Une fois le capteur appari le nombre total de p riph riques app...

Page 32: ...ssement de la temporisation param tr e si cette fonction est activ e Ce qui pr c de s applique toutes les entr es LS Les d lais ne sont pas r glables par l utilisateur D lai de temporisation activ L u...

Page 33: ...r vision du firmware puis au bout de quelques secondes la premi re option de la structure du menu voir ci dessous s affiche l cran 10 L cran passe en mode de veille au bout de 30 secondes Appuyez sur...

Page 34: ...euil de survitesse 650 4950 PPM 950 C2P Seuil de purge de CO2 Seuil de purge 700 5000 PPM 2000 A1LA Analogique 1 action faible Basse Normale Survitesse ou Purge Basse A1HA Analogique 1 action forte Ba...

Page 35: ...in V rifiez que l h lice tourne librement V rifiez le c blage interne du moteur F03 D faut capteur Humidit Temp rature Aucune valeur capteur interne Contactez le service d assistance technique r f de...

Page 36: ...36 Batterie Commutateur vitesse 4 voies 230 V...

Page 37: ...e flux centralis es 5 Interne 5 Externe Le taux de m lange des unit s de ventilation double flux d centralis es non destin es tre quip es d un piquage au niveau de l insufflation ou de l extraction S...

Page 38: ...haleur r g n ration uniquement et les taux de fuites externes pour les unit s de ventilation simple flux centralis es 5 Interne 5 Externe Le taux de m lange des unit s de ventilation double flux d cen...

Page 39: ...ARANTIE Veuillez retourner le produit dans son int gralit port pay votre fournisseur d origine ou au centre S A V Vent Axia le plus proche par la poste ou en personne Nous vous prions de l emballer co...

Page 40: ...Installatie en bedradingsinstructies Basic EP NL 8000001425 Basic Perilex C NL 8000001426 Basic Perilex D NL 8000001427 Economic EP NL 8000001428 Economic Perilex C NL 8000001429 Economic Perilex D NL...

Page 41: ...eschikt voor gebruik door personen inclusief kinderen met beperkte fysieke sensorische of geestelijke capaciteiten of die de ervaring of kennis daarvoor ontberen tenzij ze onder toezicht staan of inst...

Page 42: ...EIRP nominaal 868MHz De fabrikant waarborgt dat dit type Bluetooth radio en 868MHz radio apparatuur overeenstemt met de RED richtlijn 20145 53 EU De volledige tekst van de EU conformiteitsverklaring k...

Page 43: ...luetooth Multihome BEP BPC BPD NL 4 300 Ja Nee Ja Ja Nee Ja Nee Multihome EEP EPC EPD NL 4 368 Ja Nee Ja Ja Nee Ja Nee Multihome AEP NL 4 368 Ja Ja Ja Ja Nee Ja Ja Multihome AEC NL 4 368 Ja Ja Ja Ja J...

Page 44: ...NL 8000001177 EPD NL 8000001430 EPC NL 8000001429 EEP NL 8000001428 Wireless BE 1003000074 Uniflexplus Wireless BE 1003000075 Wireless CO2 BE 1003000077 Uniflexplus Wireless CO2 BE 1003000078 BEP NL...

Page 45: ...met lage snelheden in de luchtkanalen en gebruik afvoerventielen met een gering drukverlies voor de aansluiting met de ruimtes 1 16 De buigradius gemeten aan de binnenkant van de bocht moet minstens...

Page 46: ...46 Om de luchtdichtheid te garanderen bevestig de luchtkanalen bij installatie van de Uniflexplus 90 mm versie zodanig dat in de klikdelen telkens 3 klikken gehoord worden Afbeelding 6 Afbeelding 7...

Page 47: ...zontaal geplaatste luchtkanalen viii Verticale installatie met afvoerluchtkanalen aan de bovenkant De elektrische aansluitingen moeten aan de onderkant van de unit komen ter bescherming tegen binnendr...

Page 48: ...n de badkamerverlichting Bij de instelling van de unit kunnen via het display een uitsteltijd en een nalooptijd worden ingesteld Zie instelling van de unit op pagina 14 van dit document voor meer info...

Page 49: ...pecifieke aansluiting op de nulgeleider Deze unit is uitsluitend voor functionele doeleinden voorzien van een aarding Aansluiting Omschrijving 1 L Fasegeleider 220 240Vac 2 N Nulgeleider 3 Aardgeleide...

Page 50: ...tgang Spanningsloze schakelaar Boost Hoog indicatorschakelaar schakelt bij 6V 50mA max J Digitale uitgang 2 K D OUT 1 COM Gemeenschappelijke digitale uitgang Spanningsloze schakelaar led storingsindic...

Page 51: ...koppelfunctie op de te verbinden sensor zie de handleiding van de sensor Op de unit wordt het totale aantal verbonden apparaten weergegeven Sensoren verwijderen Reset de unit om gekoppelde sensoren te...

Page 52: ...an zodanig worden ingesteld dat hij een bepaalde tijd blijft werken nadat een bepaalde input verwijderd is Dit is uitsluitend van toepassing op LS ingangen Vochtigheid Snelle toename Deze functie reag...

Page 53: ...r in met een druk op de knop Mode 18 De instellingen kunnen worden gewijzigd met de knoppen en De knop Mode bevestigt de wijzigingen en voert verder naar de volgende menuoptie 19 De snelheden worden i...

Page 54: ...miet Max 700 5000 PPM 2000 A1LA Analoge ingang 1 lage actie Lage snelheid Normale snelheid Hoog of Maximaal Laag A1HA Analoge ingang 1 hoge actie Lage snelheid Normale snelheid Hoog of Maximaal Hoog A...

Page 55: ...aststelt Storingscode Omschrijving F01 Storing regeling Controle bij opstart unit mislukt Schakel de ventilator uit en weer aan F02 Storing motor Geen toerental Controleer of de waaier ongehinderd kan...

Page 56: ...d 0 10V Bedraad RS485 Draadloos RF868 Temperatuur vochtsensor batterij Temperatuur vochtsensor 10 30V CO2 sensor 10 30V CO2 sensor 230V PIR sensor 230V Alarm interfacemodule 230V Buiten temperatuur vo...

Page 57: ...chtkanalen 5 intern 5 extern Het mengpercentage van tweerichtingsventilatie eenheden zonder luchtkanalen die niet zijn bedoeld om te zijn uitgerust met n overgangsstuk tussen luchtkanalen aan de zijde...

Page 58: ...ntages voor externe lekkage voor nrichtingsventilatie eenheden met luchtkanalen 5 intern 5 extern Het mengpercentage van tweerichtingsventilatie eenheden zonder luchtkanalen die niet zijn bedoeld om t...

Page 59: ...aartoe gemachtigde persoon VOOR GARANTIECLAIMS Stuur het volledige product terug naar uw oorspronkelijke leverancier of het dichtstbijzijnde Vent Axia verdeelpunt via post of in persoon Zorg dat het p...

Reviews: