background image

 

 

 

 

The unit is supplied with four, 6-month Timestrip indicators. A Timestrip is a single use self-adhesive label that once 
activated will turn red over 6 months. It should be used to keep track of when the filter and cell need 
cleaning/replacement. Using the self-adhesive backing the strip can stuck near the units controls, or in a easily 
visible place. A normal cleaning schedule for a unit would be as follows: 

 

After installation  

Activate the 1st Timestrip 

After 6 months 

Clean cell, clean filter, activate 2nd Timestrip 

After 12 months 

Clean cell, clean filter, activate 3rd Timestrip 

After 18 months 

Clean cell, clean filter, activate 4th  Timestrip 

After 24 months 

Clean cell, replace filters, the new filters will be supplied with 4 additional Timestrip indicators  

 

Note: The above is the minimum requirement; more frequent cleaning intervals may be needed depending on the 
environment the unit is installed in. 

Activating the Timestrip. 

 

 

 

 

 

 

 

 

 

1. Activation: Fully squeeze the activation button between thumb and finger. A red line will appear within 1-2 
minutes to show that the Timestrip has been activated.  

2. Peel off the backing liner and stick the Timestrip to the Unit or near the controls of the unit. The location should 
make it obvious to the person responsible for maintenance that the unit needs attention. 

3. Once activated, the red dye will indicate elapsed time by moving through the white window and past each time 
marker. The progress of the red dye is irreversible and each Timestrip can only be used once. 

 

 

Summary of Contents for 14120020

Page 1: ...K Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR200WK 141...

Page 2: ...should be provided with a local isolator switch fitted with a 3A fuse capable of disconnecting all poles and having a contact separation of at least 3mm 5 These units must be earthed 6 Precautions mu...

Page 3: ...and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be connected directly to a tumble drier 5 The supply...

Page 4: ...low This provides up to 75 heat recovery from the stale extracted air 3 The power consumption for the unit is 20W trickle speed 60W normal speed and 130W boost speed 4 The three selectable speeds prov...

Page 5: ...Do not site the appliance in the vicinity of excessive levels of airborne oil or grease 7 If the unit is installed in a room containing a fuel burning appliance the installer must ensure that air rep...

Page 6: ...l control arrangement for the HR200WK unit above 2 After considering the site requirements Section 2 0 select a suitable site for the unit and controllers and work out the cable runs WARNING Before de...

Page 7: ...the top right hand side of the housing Note for the purpose of condensation drainage a prop is fitted to the underside of the housing to cause it to adopt a downwards tilt to the outside wall 4 Fix th...

Page 8: ...nductors of the cable to the appropriate terminals in accordance with the appropriate wiring diagram Fig 5 6 7 8 9 NOTE Refer to the fitting and wiring instructions provided with the controller used T...

Page 9: ...4 0 Electrical Fig 9 Fig 8...

Page 10: ...the grille surround after unscrewing its retaining screws Slide out the heat exchanger 7 Wash the grille filter and heat exchanger in warm water using a mild detergent and dry thoroughly CAUTION Keep...

Page 11: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Page 12: ...l Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Du...

Page 13: ...Notes...

Page 14: ......

Page 15: ......

Page 16: ...to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your...