Technical Specification & Installation
Sentinel Kinetic MVHR Installation & Commissioning
9
Airflow Supply
To Dwelling
Airflow Extract
From Dwelling
Airflow Supply
From Outside
Airflow Extract
To Outside
Condensate Drain
Step 5: Duct Layout:
1.
Always use a short piece of flexible ducting 100-150mm long, extended to its full length when connecting to ductwork.
2.
Securely connect this ducting to the spigots using worm-drive clips or cable ties and duct tape.
3.
Insulate any ducting passing through an unheated space to prevent any heat losses and surface condensation.
Stage 6:
Connect the 22mm condensate drain
outlet to the buildings waste water system.
A water trap must be fitted between the unit and
the rest of the waste system.
Please note you must ensure that there is a
minimum of a 3 degree downward angle to allow
water to drain away from the unit naturally.
Please Note: In areas where freezing weather
conditions occur, outlet pipes must be insulated
to avoid blockage by ice, which may cause
damage to the unit and surroundings.
Underside view of unit