Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
23
Normal Supply Screen
The Normal Supply screen enables you to set the
Normal airflow speed for the Supply fan in order to
balance out any differences in ductwork or other
installation features.
Default Normal speed = 30%
The Normal speed cannot be set below Low speed or
above Boost speed setting.
Normal Supply
30 %
Normal Extract Screen
The Normal Extract screen enables you to set the
Normal airflow speed for the Extract fan in order to
balance out any differences in ductwork or other
installation features.
Default Normal speed = 30%
The Normal speed cannot be set below Low speed or
above Boost speed setting.
Normal Extract
30 %
Low Supply Screen
The Low Supply screen enables you to set the Low
airflow speed for the Supply fan in order to balance out
any differences in ductwork or other installation
features.
Default Low speed = 20%
The Low speed cannot be set below 1% or above
Normal speed setting.
Low Supply
20 %
Low Extract Screen
The Low Extract screen enables you to set the Low
airflow speed for the Extract fan in order to balance out
any differences in ductwork or other installation
features.
Default Low speed = 20%.
The Low speed cannot be set below 1% or above
Normal speed setting.
Low Extract
20 %
Cooker Hood Supply & Extract Screens
The Cooker Hood Supply & Extract screens
are
non-functional.
Ckr Hood Supply
30%
Ckr Hood Extract
100%