Installation and Wiring Instructions for the Azur Range of Extractor Fans.
IMPORTANT:
READ THESE INSTRUCTIONS
BEFORE COMMENCING THE
INSTALLATION
DO NOT install this product in areas where the following may be present or occur:
•
Excessive oil or a grease laden atmosphere.
•
Corrosive or flammable gases, liquids or vapours.
•
Ambient temperatures higher than 40°C or less than –5°C.
•
Possible obstructions which would hinder the access or removal of the fan.
SAFETY AND GUIDANCE NOTES
A.
All wiring to be in accordance with the current I.E.E. Regulations, or
the appropriate standards of your country and
MUST
be installed by
a suitably qualified person.
B.
The fan should be provided with a local isolator switch capable of
disconnecting all poles, having a contact separation of at least 3mm.
C.
Ensure that the mains supply (Voltage, Frequency, and Phase)
complies with the rating label.
D.
The fan should only be used in conjunction with the appropriate
Vent-Axia products.
E.
The fan should only be used in conjunction with fixed wiring.
F.
When the fan is used to remove air from a room containing a fuel-
burning appliance, ensure that the air replacement is adequate for
both the fan and the fuel-burning appliance.
G.
The fan should not be used where it is liable to be subject to direct
water spray for prolonged periods of time.
H.
Where ducted fans are used to handle moisture-laden air, a
condensation trap should be fitted. Horizontal ducts should be
arranged to slope slightly downwards away from the an.
I.
This appliance is not intended for use by people (including children)
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given
supervision or instructions concerning use of the appliance by a
person responsible for their safety.
J.
Children should be supervised to ensure that they do not play with
the appliance.
K.
Stationary appliances not fitted with means for disconnection from
the supply mains having a contact separation in all poles that
provide full disconnection under over voltage category III, the
instructions state that means for disconnection must be
incorporated in the fixed wiring i
2
n accordance with the wiring rules.