CE-1-11/00
4.0 Electrical
10
4.1
Electrical Connections
230V 50Hz 12W (normal) 31W (boost)
NOTE:
Wiring must be via a 3A fused
switched spur with a 3mm contact separation
in each pole. The wiring should be suitably
(BASEC or HAR) approved cable of
appropriate current carrying capacity.
HR
100R Terminals 3 amp fused supply
L
L
N
Neutral
Live
Black
Brown
Blue
Green/Yellow
Earth
1
2
HR
100R Terminals 3 amp fused supply
L
L
N
Neutral
Live
Black
Brown
Blue
Green/Yellow
Earth
1
2
HR
100R Terminals
3 amp fused supply
L
L
N
Neutral
Live
Black
Brown
Blue
Green/Yellow
Earth
1
2
L
N
HR
100R Terminals
3 amp fused supply
L
L
N
Neutral
Live
Earth
1
2
HR
100R Terminals
3 amp fused supply
L
L
N
Neutral
Live
Black
Brown
Blue
Green/Yellow
Earth
1
2
1
0
2
Continuous Normal Speed
Continuous Boost Speed
VCON100: Manual Normal to Boost Speed
Switching and ON/OFF Control
NBSW and PCSW: Manual Normal to Boost
Speed Control
HS6: Automatic Normal to Boost Speed Control
1
0
2
L
SL
N
TIM2 Terminals
Neutral
Link
Light fitting if
appropriate
Switched live
Mains via switched
fused spur
Live
Earth
HR
100R
Terminals
L
L
N
HR
100R
Terminals
3 amp fused
supply
Neutral
Live
Switched Live
Light
Earth
L
L
N
1
2
For units switching to boost on operation of a light switch, an
in-line timer (order code TIM2) should be wired into the circuit
as shown below.
Automatic Control
The
HR
100R unit operates on continuous trickle ventilation.
Operation of switch turns unit to boost ventilation. When switch
is turned off units continue to operate on boost for a preset
period - adjustable 2-30 minutes.
The
HR
100R MUST NOT be wired in conjunction with a light
switch, units will fail.