background image

6. Withdraw  the heat exchanger  from the housing by grasping and gently but firmly pulling on its 
central vertical member. 

7. Offer the housing to the inner mounting surface and, with the duct spigot located over the duct, 
mark the two fixing hole positions on the mounting surface. 

8. Prise the grille out of the grille assembly and remove the insect screen. 

9. Offer the grille base to the external mounting surface and,with the duct spigot located inside the 
duct, mark two of the four fixing hole positions on the mounting surface. 

10.Suitably drill and plug the fixing holes in both mounting surfaces. 

11.Pass the supply cable through the grommet in the rear face or top face of the housing and fix the 
housing to the inner mounting surface using suitable round head woodscrews. 

12.Fix the grille base to the external wall surface also using suitable round head woodscrews. 

13.Replace the insect screen and grille in the grille base. The grille blades must slope downwards 
away from the external mounting surface to shed rainwater. 

WIRING INSTRUCTIONS (SEE FIG.5) 

1. Ensure the mains electrical supply is switched off. 

2. Remove the terminal block cover after unscrewing the retaining screw. 

 

3. Remove the minimum amount of sheath and insulation from the supply cable and leads.   
Slacken the cable clamps and feed the cable through the clamps. Connect the conductors,coloured 
red-live(L),black-neutral(N) and  green/yellow-earth(E/    ),  to the appropriate terminals, marked L1, 
L2, N and E/    of the terminal block  in accordance  with  the  wiring  arrangements shown in Fig. 5.

 

4. Position the cable in the cable clamps such that the cable sheath will be clamped and tighten the 
cable clamp nuts to secure the cable in position. 

5. Replace the terminal block cover and tighten the retaining screw. 

6. Replace the heat exchanger. 

7. For top cable entry make a cutout in the top of the cover to clear the cable. 

8. Refit the cover and tighten the four retaining screws. 

9. Switch on the mains electrical supply and check the fan operation. 

 

CLEANING 

Apart from removing odours, providing fresh air and recovering heat this appliance extracts airborne 
impurities such as dust, dirt and grease.  These gradually bulid up and detract  from the efficiency 
and appearance of the appliance.  Therefore, to ensure peak performance, the appliance should   
be cleaned regularly at periods determined by the level of contamination experienced and according 
to the following procedure: 

Summary of Contents for HR100S

Page 1: ...HR100S Heat Recovery Ventilation Unit Surface mounting two speed heat recovery extract and intake unit for bathrooms and toilets Installation and Maintenance Instructions Stock Ref No HR100S 141 10 010 ...

Page 2: ...ected and tested by a suitably qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur fitted with a 3A fuse having a contact separation of at least 3mm 5 These units must be earthed 6 Precautions must be taken to avoid the back flow of gases into the building from the o...

Page 3: ...pply will energise both motor windings and cause the motor to overheat and cutout INSTALLATION GUIDANCE 1 The installer is responsible for the installation and electrical connection of the system on site It is the responsibility of the installer to ensure that the equipment is safely and securely installed and left only when mechanically and electrically safe 2 All regulations and requirements mus...

Page 4: ... work out the cable runs When using surface wiring which is not contained in conduit the wiring must be securely anchored to the mounting surface Install the cable runs in conjunction with a fused and switched connection unit located in the vicinity of where the ventilation unit will be sited Ensure that the cables for the ventilation unit extend at least 400mm from the mounting surface FITTING IN...

Page 5: ... 2 Remove the terminal block cover after unscrewing the retaining screw 3 Remove the minimum amount of sheath and insulation from the supply cable and leads Slacken the cable clamps and feed the cable through the clamps Connect the conductors coloured red live L black neutral N and green yellow earth E to the appropriate terminals marked L1 L2 N and E of the terminal block in accordance with the w...

Page 6: ...he housing by grasping and gently but firmly pulling on its central vertical member 5 Wash the cover filter and heat exchanger in warm water using a mild detergent and subsequently dry them thoroughly Keep water away from all electrical components and wiring within the appliance 6 Replace the heat exchanger 7 Replace the filter in the cover 8 Refit the cover and tighten the four retaining screws 9...

Page 7: ......

Page 8: ......

Page 9: ......

Page 10: ......

Page 11: ...3 h 0 56 Control Factor Control Typology CTRL Typology Control Factor CTRL 1 00 Control Typology Manual Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs TBC Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct connection on either supply or extract air side TBC Filter Warning RVU ...

Page 12: ...rating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your original supplier or nearest Vent Axia Centre by post or personal visit Please ensure that it is adequately packed and accompanied by a letter ...

Reviews: