11
5.0 Installation Requirements
5.1
Location
1. The cooker hood MVHR unit is only suitable
for installation above a domestic cooker or
domestic hob. The HR205 must be sited a
minimum of 700 mm above the cooker/hob.
2. The exhaust duct must pass through an
outside wall or roof and discharge to atmosphere
in a suitable position .The clean air inlet duct
must pass through an outside wall or roof and be
suitably positioned to provide an adequate fresh
air supply from atmosphere.
5.2
Site requirements
1. For the HR205 a flat vertical area 1332mm
high x 600mm wide is required for installation.
For the HR204 a flat vertical area 692mm high x
562mm wide is required for installation.
Important: The HR204 is not suitable for
installation above any cooking appliance
or with any extraction system servicing
a cooking appliance.
2. Before installation consideration must be
given to the position of the ductwork
connections, the electrical connection and the
condensate pipe connection.
Warning: Please check the information on
the data plate is compatible with local
supply conditions.
3. The installation must be carried out by a
competent person and be in accordance with the
relevant Building regulations (Scotland)
(consolidation), the Local building regulations,
the current I.E.E. Wiring regulations.
Reference should also be made to the BRE
digest 398 and CIBSE guidelines.
Warning: The addition of anything that
may interfere with the normal operation of
the appliance without the express written
permission of Vent-Axia Ltd could
invalidate the appliance warranty and
infringe regulations.
Warning: If the unit is fitted in a room
containing a bath or shower then
reference should be made to the current
I.E.E. Wiring Regulations and Building
Regulations.
Summary of Contents for HR205
Page 29: ...29 This page is intentionally blank...
Page 36: ...372705C 0208...