background image

32

11.0  Fault Finding

HR204 - Main Unit Fault Finding Chart

START

YES

NO

1
2
3
4
5
6

Controller

Connector

Block

Fan

Plug

D

3

2

1

G

F

B

A

C

1
2

1
2

1
2
3

O

B

C

L

N

Fuse

(3.15AT)

WHC0037A

Ensure continuity

between terminals

D5 & A1

and between

D6 & A2

Check mains

supply.

Is there

mains voltage

across terminals

A1/A2?

YES

NO

Investigate cause

and

rectify fault

Is the

fuse on the

controller

O.K.

YES

NO

Disconnect wires

from terminals

F1, F2 & F3.

Ensure voltage
selector wire is

correctly engaged.

Replace controller

Is the

voltage across

terminals B1 &

B2 between 80v

& 160v?

NO

Is the voltage

across F1 & B2

between 80v

& 160v?

Replace controller

NO

Is there mains

voltage between

F2 and B2

YES

NO

See Fan Fault

Finding Chart

Check external

control wiring.

Refer to 204 wiring

diagram (section 7)

Reconnect wires

to terminals

F1, F2 & F3.

Rectify fault
on wiring to

external control

Check

external

control,

rectify or

replace

as

necessary.

NO

Do the

external controls

have a mains supply

from F2 & reduced

voltage supply

from F1

Are both fans

operating?

YES

YES

YES

L

N

160

Voltage Selector Wire

140
120
100

80

Replace fuse

3.15AT

Before starting FAULT FINDING

 carry out preliminary electrical systems checks

i.e. Earth Continuity, Polarity, Short Circuit

and Resistance to Earth.

Ensure all external controls are operating
and are set to normal running. Ensure that
a mains electrical supply is available to the
unit.

Refer to diagrams below to
identify terminals on components
(e.g. A1, D3 etc).

Note 1

Electricity supply must be
isolated and Fan Motor
temperature must be less than
100˚ to allow thermal trip to
reset.

WARNING

If the Fan thermal trip
has operated, check the
entire system and unit
for correct installation.
Check all ducting outside &
terminals for blockages.

IMPORTANT

When investigating
overheating allow the unit to
run long enough for any fault
to become apparent.

Summary of Contents for HR205

Page 1: ...Please leave these instructions with the user Whole House Ventilation System with Heat Recovery and Cooker Hood HR205 User Installation Servicing Instructions...

Page 2: ...ayout 3 0 Technical Data 4 0 Appliance Operation 5 0 Installation Requirements 6 0 Installation 7 0 Wiring Diagrams 8 0 Commissioning 9 0 Maintenance 10 0 Changing Components 11 0 Fault Finding 12 0 S...

Page 3: ...e considered before siting the extract and inlet vents the vents must also be sited away from other flue terminals ventilators etc on the outside of the dwelling In addition there shall be adequate ve...

Page 4: ...ical ventilation with heat recovery MVHR unit designed solely to operate with the Vent Axia telescopic cooker hood The unit provides continuous extraction of stale air from the dwelling typically from...

Page 5: ...after thoroughly drying 1 2 Air Inlet Filter HR204 HR205 Fig 4 1 Lift off the front door panel by releasing the two hand screws and lifting upwards 2 Remove the air inlet filter by pulling forwards 3...

Page 6: ...or RH 4 Electrical Control Transformer 5 Fuse 3 15amp fast blow 6 Terminal Block 7 Overheat Sensor 8 Lower Fixing Hole 9 Fire Damper 10 Condensate Drain 15mm 11 Condensate Tray 12 Alternative outlet f...

Page 7: ...RH 4 Electrical Control Transformer 5 Fuse 3 15amp fast blow 6 Terminal Block 7 Lower Fixing Hole 8 Alternative outlet for condensate bottom 9 Condensate Drain 15mm 10 Condensate Tray 11 Alternative...

Page 8: ...weight kg 20 6 16 7 Voltage tappings Power consumption watts Power consumption watts Lights off Lights on 80 16 96 16 100 27 107 27 120 40 120 40 140 52 132 52 160 65 145 65 230 111 191 111 Duct conne...

Page 9: ...t gives the ventilation rates at each fan speed setting compared to the pressure drop of the system 0 50 100 150 300 350 250 200 0 20 10 30 50 70 40 60 80 90 100 110 120 130 140 150 160 170 180 190 20...

Page 10: ...trip in the fan senses temperature rise and breaks the electrical supply to the motor This can only be reset by disconnecting from the mains supply If the overheat thermostat senses an elevated rise...

Page 11: ...y extraction system servicing a cooking appliance 2 Before installation consideration must be given to the position of the ductwork connections the electrical connection and the condensate pipe connec...

Page 12: ...house 2 The duct work system should be sized and installed to minimise the pressure loss along it 3 Using larger diameter pipes and keeping the number of bends and fittings used to a minimum will redu...

Page 13: ...70495 is available for manual boost control remote from the unit An optional pull cord boost switch PCSW Part No 370278 is available for manual boost control remote from the unit 5 6 Electrical supply...

Page 14: ...um Top Clearance for servicing 200 Minimum Side Clearance 5 Minimum Side Clearance 5 Clearances HR204 Minimum Bottom Clearance 100 Minimum Front Clearance for servicing 250 280 Clearances HR205c Minim...

Page 15: ...ket in the protective box taking care to route the cables as shown Fig 16 Clip the box together and secure using the screws provided Locate the large cable grommet in the hole and ensure it is seated...

Page 16: ...s before engaging the final screw 6 5 Making the condensate connection 1 The condensate connector is suitable for 15 mm pipe 2 The condensate pipe should incorporate a water trap to prevent foul air b...

Page 17: ...the electrical connection Warning This appliance must be earthed 1 The normal running speed of the fans is set at 120v 2 The unit must be set to the appropriate voltage as determined by air flow requ...

Page 18: ...gr gr gr gr w w br br w br br Brown g y Green Yellow p Purple bk Black Key Colors b Blue gr Grey r Red w White L N L L N N Fuse 3 15AT Fan air in r r r r b b g y g y g y b gr gr br br c boost speed 2...

Page 19: ...Blue gr Grey r Red w White L N L N Fuse 3 15AT Fan air in r r r r b b g y g y g y Mains In 230v g y br b g y br b b b b br br b b b 1 2 3 4 Remove Link To Cooker Hood Earth for Inspection Panel Fan ai...

Page 20: ...nal Controls Fan air out Controller L N 160 140 120 100 80 O B C br br br Brown g y Green Yellow p Purple bk Black Key Colors b Blue gr Grey r Red w White L N L L N N Fuse 3 15AT Fan air in r r r r b...

Page 21: ...3 15AT Fan air in r r r r b b g y g y g y Mains In 230v g y br b g y br b b b b br br b b b 1 2 3 4 Earth for Inspection Panel Fan air out Controller L N 160 140 120 100 80 O B C br Brown g y Green Ye...

Page 22: ...eed 4 Pull the telescopic hood forward The unit will now switch to boost speed 5 Check the operation of the cooker hood lights 8 1a Prepare for commissioning HR204 1 Refit the front door panel by hook...

Page 23: ...from the appliance 7 Check the flow rate and adjust if necessary the remaining inlet valves 8 Repeat the checks and adjust until the system is correctly balanced Note If the flow rates have been achi...

Page 24: ...red Check the fire damper is in satisfactory condition and unaffected by debris and fat deposits Replace if necessary 7 Check both fans fan compartments and exhaust duct outlets for deposits Clean as...

Page 25: ...pliance will run on normal setting Extend the hood and the appliance will switch to boost setting With the appliance on boost check the operation of the cooker lights 14 Check the condition of the duc...

Page 26: ...Lift off the front door panel by releasing the two hand screws and lifting upwards 2 Remove the bottom electrical cover by releasing the 3 screws pulling the panel forwards and disconnecting the earth...

Page 27: ...te and lift to remove 3 Release the clip on the plastic plug and disconnect the plug 4 Slacken the two rear fan bracket screws 5 Remove the two front fan bracket screws and remove the fan assembly 6 D...

Page 28: ...the heat exchanger forwards and remove 3 Remove the four heat exchanger seals taking care to remove all the old adhesive backing 4 Fit the new seals ensuring they make good contact with the location...

Page 29: ...29 This page is intentionally blank...

Page 30: ...nough for any fault to become apparent 1 2 3 4 5 6 Controller Connector Block C Hood Plug Fan Plug D E 3 2 1 G F B A C 1 2 1 2 1 2 3 O B C L N Fuse 3 15AT WHC0035A Ensure the Cooker Hood is closed Ens...

Page 31: ...adjusted correctly Is there adequate airflow at the appliance inlets and outlets YES YES NO Ensure continuity across cooker hood plug and lead Replace cooker hood Replace bulbs Max 40 watts Replace bu...

Page 32: ...ault on wiring to external control Check external control rectify or replace as necessary NO Do the external controls have a mains supply from F2 reduced voltage supply from F1 Are both fans operating...

Page 33: ...t system and terminals for blockages or damage Ensure terminals are adjusted correctly Is there adequate airflow at the appliance inlets and outlets Replace bulbs Max 40 watts Unit operating satisfact...

Page 34: ...fan connector G2 G3 Is the capacitor reading approximately 2 F NO NO Has the fan thermostat trip operated see note 1 Fan has overheated Investigate the cause and rectify Replace fan section 10 3 NO Re...

Page 35: ...filter 7 372736 Heat exchanger 8 372737 Heat exchanger seals 4 off 9 372739 Outer door assembly 10 372741 Cooker hood seal 11 372743 Cooker hood filters set of two 12 372748 M5 wing screw 13 372777 L...

Page 36: ...372705C 0208...

Reviews: