background image

 

 

 

The unit is supplied with four, 6-month Timestrip indicators. A Timestrip is a single use self-adhesive label that once 
activated will turn red over 6 months. It should be used to keep track of when the filter and cell need cleaning/replacement. 
Using the self-adhesive backing the strip can stuck near the units controls, or in a easily visible place.  

A normal cleaning schedule for a unit would be as follows: 

After installation  

Activate the 1st Timestrip 

After 6 months 

Clean cell, clean filter, activate 2nd Timestrip 

After 12 months 

Clean cell, clean filter, activate 3rd Timestrip 

After 18 months 

Clean cell, clean filter, activate 4th  Timestrip 

After 24 months 

Clean cell, 

replace filters

, the new filters will be supplied with 4 additional Timestrip indicators  

 

Note: The above is the minimum requirement; more frequent cleaning intervals may be needed depending on the 
environment the unit is installed in. 

Activating the Timestrip. 

 

 

 

 

 

 

 

 

 

1. Activation: Fully squeeze the activation button between thumb and finger. A red line will appear within 1-2 minutes to 
show that the Timestrip has been activated.  

2. Peel off the backing liner and stick the Timestrip to the Unit or near the controls of the unit. The location should make it 
obvious to the person responsible for maintenance that the unit needs attention. 

3. Once activated, the red dye will indicate elapsed time by moving through the white window and past each time marker. 
The progress of the red dye is irreversible and each Timestrip can only be used once. 

 

 

 

 

 

 

 

 

Summary of Contents for HR300

Page 1: ...00 Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR300 3703...

Page 2: ......

Page 3: ...d by a suitably qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur...

Page 4: ...stallation and during any subsequent servicing and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be conn...

Page 5: ...Contents Section Page 1 0 Introduction 5 2 0 Site Requirements 6 3 0 Installation 7 4 0 Electrical 9 5 0 Maintenance 10...

Page 6: ...power consumption for the unit is 108w 4 The twin impeller and heat exchanger arrangement simultaneously supplies and extracts air while transferring heat from the stale exhaust airflow to the fresh...

Page 7: ...ply is compatible with the rating label attached to the product 8 The unit must be sited such that the ambient temperature will not exceed 40 C 9 Do not site the appliance in the vicinity of excessive...

Page 8: ...ect an approved electrical control arrangement for the HR300 unit above 2 After considering the site requirements Section 2 0 select a suitable site for the unit and controllers and work out the cable...

Page 9: ...the two fixing screws provided NOTE Ensure the fixings DO NOT inhibit removal or replacement of the heat exchanger 4 Make good around the case 5 Fit the bezel on the inside to cover the making good b...

Page 10: ...HR300 is supplied with a length of cable attached from the factory This can be extended with the use of 4 core cable as required 5 Connect the wires as shown in Fig 7 to a Switched fused spur or a co...

Page 11: ...from rear of grille 6 Slide out the heat exchanger Fig 8 7 Wash the grille filter and heat exchanger in warm water using a mild detergent and dry thoroughly CAUTION Keep water away from all electrical...

Page 12: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Page 13: ...Typology Central Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Inter...

Page 14: ...Notes...

Page 15: ...Notes...

Page 16: ...ating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE P...

Reviews: