background image

3.0 Installation

 

 

 

 

CG

-1

-1

/0

1

 

 

 

3.1 

Controllers

 

 

1. The HR300 unit can be installed in conjunction 
with a number of controllers.

  

 

VCON6(370356): 

The VCON6 controller can be 

used to provide Off/Low/Normal/Boost/Sensor 
control. (The HS6 humidistat or TIM2 over-run 
timer can be used in conjunction with the VCON6 
controller to provide automatic control. 

150VA (

563538): 

The 150VA transformer, 

when used with a trickle/boost switch (455213), 
allows for a trickle and boost speed to be 
selected. Only terminals providing 140V or 
higher should be used as the unit will not 
operate reliably bellow 140V. 

Ecotronic 1.5A controller (W300310): 

Provides variable speed control and on off and 
auto (sensor) modes. 

TIM2(370346): 

The TIM2 is an overrun timer 

which can also be used to control the HR200 
unit via a remote sensor e.g. Humidity Sensor.

 

 

3.2 

Initial Preparation

 

 

1. Select an approved electrical control 
arrangement for the HR300 unit (above).

 

 

2. After considering the site requirements 
(Section 2.0), select a suitable site for the unit 
and controllers and work out the cable runs.

 

 

WARNING: 

Before deciding on the final position 

for the unit, check there are no buried cables, 
pipes or obstructions on the outside wall.

 

 

Cable requirements: 

Suitably (Basec or Har) 

approved four core cable of appropriate current 
carrying capacity.

 

 

3. Install the cable runs and appropriate 
controllers in conjunction with a fused connection 
unit. Contact gap must not be less than 3mm.

 

 

4. Working from the inside, mark out the 
position of the mounting hole - 280mm wide x

 

380mm high (see Fixing Template).

 

 

5. Carefully cut the holes in the inner and outer 
brick courses to form a suitable aperture to 
receive the unit. Ensure that this is level.

 

 

NOTE: 

Bricks will cut more easily and 

accurately if a series of holes are drilled close 
together along the marked lines.

 

 

 

 

 

 

6. Remove the grille, heat exchanger, from the 
unit (Fig. 3).

 

 

 

 

Heat Exchanger

Grille

 

Fig.3. 

Summary of Contents for HR300

Page 1: ...00 Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR300 3703...

Page 2: ......

Page 3: ...d by a suitably qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur...

Page 4: ...stallation and during any subsequent servicing and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be conn...

Page 5: ...Contents Section Page 1 0 Introduction 5 2 0 Site Requirements 6 3 0 Installation 7 4 0 Electrical 9 5 0 Maintenance 10...

Page 6: ...power consumption for the unit is 108w 4 The twin impeller and heat exchanger arrangement simultaneously supplies and extracts air while transferring heat from the stale exhaust airflow to the fresh...

Page 7: ...ply is compatible with the rating label attached to the product 8 The unit must be sited such that the ambient temperature will not exceed 40 C 9 Do not site the appliance in the vicinity of excessive...

Page 8: ...ect an approved electrical control arrangement for the HR300 unit above 2 After considering the site requirements Section 2 0 select a suitable site for the unit and controllers and work out the cable...

Page 9: ...the two fixing screws provided NOTE Ensure the fixings DO NOT inhibit removal or replacement of the heat exchanger 4 Make good around the case 5 Fit the bezel on the inside to cover the making good b...

Page 10: ...HR300 is supplied with a length of cable attached from the factory This can be extended with the use of 4 core cable as required 5 Connect the wires as shown in Fig 7 to a Switched fused spur or a co...

Page 11: ...from rear of grille 6 Slide out the heat exchanger Fig 8 7 Wash the grille filter and heat exchanger in warm water using a mild detergent and dry thoroughly CAUTION Keep water away from all electrical...

Page 12: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Page 13: ...Typology Central Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Inter...

Page 14: ...Notes...

Page 15: ...Notes...

Page 16: ...ating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE P...

Reviews: