Installation
Integra Plus ECA MVHR Installation & Commissioning
10
Fig 4. Water trap details
WATER TRAP
CONDENSATION
DRAIN FROM UNIT
SILICON SEALER
FALL TOWARDS
THE BUILDINGS
DRAINAGE SYSTEM
A
NOTE:
INSTALL THE CONDENSATE DRAINAGE TUBING IN
ACCORDANCE WITH THE DIAGRAM.
ENSURE THE WATER TRAP IS BELOW THE DRAIN
ELBOW OUT LET "A"
To mount the unit on joists:
Place the unit on a suitable platform across joists and attach the appropriate cabling, drainage and ductwork to the unit, with the
Vent-Axia badge facing up. For optimum performance, ensure the ductwork does not turn 90° directly off the spigots. The unit
should, for optimum drainage, be tilted by 3°- 5° towards the drain side. See Fig. 3a.
Ceiling mounted:
.
Invert the unit with the Vent-Axia logo facing down and attach the unit securely to the rafters. For optimum performance, ensure
the ductwork does not turn 90° directly off the spigots. The unit should, for optimum drainage, be tilted 3°- 5° towards the drain
side. See Fig. 3b.
Please note - the location and position of installation for the unit must be decided before any drainage knockouts are removed, as
they cannot be refitted.
5. Having decided upon a location and position remove the knock out for the condensate drain, this must be at the lowest point.
Connect the drain of the ventilation unit to the drainage system using suitable ‘U’-bends (see fig 4).
6. Install suitable internal and external grilles/ terminals and connect them to the ventilation unit using suitable 150mm ducting. If
flexible ducting is used, it should be stretched in order to obtain the best performance.
Summary of Contents for Integra Plus EC
Page 2: ......
Page 18: ...Notes...
Page 19: ...Integra Plus ECA MVHR Installation Commissioning 19 Notes...